Co.,Ltd.
Triple IR Flame Detector
RFD-3000X
Document No. Manual
–
3000X (Rev. 05) March 2012
- 39 -
Scope of Inspection
Power supply
status checking
- If a bulb of the test lamp no.1 or no. 2 is not functioning,
it means the test lamp is defected.
- A bulb of the test lamp no.1 is not flashing, weaker the intensity
of radiation. If lamp no. 2 is not functioning please re-charge it
and use thereafter.
[Table 31] Lighting Status of the test lamp
Product Operation Status Vary According to Testing Conditions
Status
Operate or Output Status
Before connecting
power
- Fault Relay signal open (de-energized)
- All LED OFF
After
connecting
power
connecting
power
- Fault Relay signal open (de-energized)
- After LED blinking sequentially 3 second (Orange → Red →
Green, clockwise),10 seconds of self diagnosis test.
Normal
- Fault Relay signal close (energized)
- All output, "normal" signal output
- Green LED light ON
Fire
- All output "Alarm" signal
Note. Except alarm relay output of signals, all output signals depend on programmable
dip-switch setting.
[Table 32] Product Operation Status Vary According to Testing Conditions