Weights (kg)
( table 1)
3.0
P
RACTICAL
A
PPLICATION
3.1
Heat exchanger compartment size.
3.1.1 The duct section or air handler compartment must be
sized in accordance with the dimensions given in
table 2 with reference to figure 4.
Mounting flanges on the modules RHC 8000(M) RJL
& DJL allow easy installation.
3.1.2 The heating module may only be fitted as shown in
figure 5. Alternative orientation is
not
allowed.
Table 2. Dimensions of enclosures (duct channel) for RHC 8000 heating modules re. fig 4
Duct channel & controls compartment
Model
H
H1
Y
Y2
W
W1
E
(min)
8030 06
531
461
1244
1170
400
400
400
8045 09
741
671
1244
1170
400
400
400
8050 06
531
461
1844
1770
400
400
400
8060 12
950
880
1244
1170
400
400
400
8075 09
741
671
1844
1770
400
400
400
8075 15
1160
1070
1244
1170
400
400
400
8090 18
1369
1299
1244
1170
400
400
400
8100 12
950
880
1844
1170
400
400
400
8125M.15
1272
1202
1844
1770
400
460
420
8150M 18
1481
1411
1844
1770
400
460
420
8175M.21
1691
1621
1844
1770
400
460
420
8200M.24
1900
1830
1844
1770
530
530
470
(*)
The dimension ‘E’ is applicable for RJL units (outdoors) when dealing with the standard terminal outlet (PN 60 5712
300.with length 300mm. When dimension ‘E’ is increased, the RJL outlet pipe can be extended to max. length of
1000mm using
⇔
100mm, thick wall seamless aluminium pipe or to max. length of 1000mm using
⇔
130mm, thick
wall seamless aluminium pipe for the 8000M models.
Figure 4 : Compartment dimensions
For horizontal airflow
Type
8030 06
8045 09
8050 06
8060 12
8075 09
8075 15
8090 18
8100 12
Unit
kg
60
87
80
120
110
140
160
145
Packaging kg
16
16
20
16
20
16
16
20
Total
kg
76
103
100
136
130
156
176
165
Type
8125M.15 8150M.18 8175M.21 8200M.24
Unit
kg
200
230
265
305
Packaging kg
35
35
35
35
Total
kg
235
265
300
340
(n° 59018)