0710RHC8-JLNLEN
14
/
36
7.0 E
LECTRICAL
E
QUIPMENT
Warning : Ensure that when installing electrical
wiring or cables no contact is made with the
burner, heat exchanger or flue arrangement.
Cables or wires must be securely fixed so that
they cannot move. To protect supply cables as
good as possible we recommend to install them
at the left side of the control compartment.
7.1.1 The RHC 8000(M) heating module has been
fully tested prior to leaving the manufacturer.
The constructor shall not make changes to
the wiring supplied with the module.
Electrical connections may only be made
using the terminals provided and strictly in
accordance with wiring diagram provided
with the module.
7.1.2 RHC 8000(M) electrical controls
are
phase
sensitive 230V 1N 50 Hz. The appliance
must be
earthed
after the installation has
been completed and earth continuity test
must be carried out.
7.1.3 The electrical equipment of the module
complies with the requirements of: EN
60335-1, EN60730-1 and EN61058-1 or to
relevant amendments. The constructor must
also comply with these requirements when
fitting the module.
7.1.4 The protection of jacket less appliances
conforms to protection code IP 20. The
constructor must ensure that protection
accordingly to at least IP 45 is fulfilled and
mark his data/rating plate accordingly.
NOTE: IP 45 provides:
a) Personal protection against contact with
electrical components within the construction;
b) Degree of protection within the construction
against ingress of water;
7.1.5 The constructor shall test and inspect fully
the total appliance prior to supply including
the following:
a) Earth continuity (re: CENELEC 289)
b) Di-electric strain (re: CENELEC 289)
c) Function of all electrical components
and
securities
and
operational
inspection
d) Heat input and test for good and clean
combustion
e) Auxiliary equipment to be supplied as
part of the appliance
f) Soundness of the total gas circuit
Attention : all passages for gas pipes, etc. to
the control compartment must be completely
sealed !
8.0 C
OMBUSTION SYSTEM
RHC
8000(
M
)
RJL
‘
OUTDOOR
’
8.1.1 Inlets for combustion air and flue outlets
shall be so designed so that when an
appliance is finally installed their
termination shall be at least 500mm
above deck/ground level.
8.1.2. The heating modules are delivered with all
parts necessary for the construction of the
jacket so that combustion can take place
safely and in line with the Gas Appliance
Directive.
Included with the heating module RHC 8000
(except for 8075 15 & 8090 18) are :
-
Dia 100 terminal outlet (length 300mm)
(PN°60 50712 300)
-
90° elbow with sealing ring
(dia 100)
(PN 60 50733 100)
-
Flue outlet combustion sealing ring (dia 100)
(PN
06 22786 104)
-
Combustion air inlet protection grill
(PN 90 79050)
- Gas tube sealing ring
(PN 06 22783 125)
Included with the heating module RHC 8075 15
& 8090 18 are
:
-
Dia 130 terminal outlet (length 282mm)
(PN°60 50712 130282)
-
90° elbow with sealing ring
(dia 130)
(PN 60 50733 130)
-
Flue outlet combustion sealing ring (dia 130)
(PN 06 22786 134)
-
Combustion air inlet protection grill
(PN 90
79344 07 for 8075 15 & PN 90 79344 09 for 8090
18))
- Gas tube sealing ring
(PN 06 22783 125)
Included with the heating module RHC 8000M
are
:
-
Dia 130 terminal outlet (length 282mm)
(PN°60 50712 130282)
-
90° elbow with sealing ring
(dia 130)
(PN 60 50733 130)
-
Flue outlet combustion sealing ring (dia 130)
(PN 06 22786 134)
-
Combustion air inlet protection grill
(PNs 90
79344 10 for 8125M, 90 79344 14 for 8150M, 90
79344 12 for 8175M & 90 79344 08 for 8200M)
- Gas tube sealing ring
(PN 06 22783 054)