background image

0710RHC8-JLNLEN 

   

 

 

 

 

 

26

/

36

 

 

12.0

 

I

NSTALLATION  OF 

RHC

  UNITS  IN 

 

SERIES

 

 

   

12.1 

 General 

 

12.1.1  Two  or  three  RHC  units  can  be  installed  in 

series.  Units can be bolted together using the 

pre-punched holes in the duct flanges (see fig. 

3  for  dimensions  B  and  C).    Apply  a  sealant 

between two units in order to avoid air leakage. 

 

12.1.2   Each  individual  unit  requires  its  own 

combustion circuit as described in sections 8.0 

& 9.0. 

 

12.1.3   Instructions concerning the burner and controls 

section  (see  section  5.0)  must  be  followed.  

The  controls  sections  of  the  2  or  3  units  in 

series  can  be  combined,  resulting  in  one 

enclosure. 

 

12.1.4   Perforated inlet plates : 

a) 2 units in series : 

*At  higher  airflow  conditions  (above  V2) 

(table  8a)  the  perforated  inlet  plates  are 

NOT required and both must be removed. 

*For  airflow  conditions  below  V2,  the  RHC 

unit  at  the  air  inlet  side  must  still  have  a 

perforated inlet plate.  The perforated plate 

of the second unit must be removed. 

 

b) 3 units in series : 

With  3  units  in  series,  the  perforated  inlet 

plates are NOT required.  Consequently, all 

3 perforated inlet plates must be removed. 

 

12.2 

Limitations for use 

 

12.2.1   Minimum  airflow  requirement  through  heat 

exchanger enclosure : For RHC units, installed 

in series, the minimum airflow duty through the 

heat exchanger enclosure (see fig. 4 – table 1) 

must  be  observed  as  indicated  in  table  8a  & 

8b. 

 

12.2.2   Maximum  airflow  through  heat  exchanger 

enclosure  :  The  recommendations  as 

described  in  section  4.1.2  are  applicable  for 

RHC units when installed in series.  Checking 

the  possibility  of  condensation  forming  within 

the  tubes  must  be  done  (heating  section  by 

heating  section),  taking  into  account  the 

expected  minimum  inlet  temperature  and  the 

heat  output  conditions  for  each  individual 

heating section. 

Table 8a  

 

Minimum airflow requirements for 2 RHC 

units in series

 : 

Model 

V1 

(m

³

/h) 

V2 

(m

³

/h) 

2x 8030 06 

3750 

4400 

2x 8045 09 

5650 

6600 

2x 8050 06 

6200 

7150 

2x 8060 12 

7500 

8750 

2x 8075 09 

9300 

10790 

2x 8075 15 

9300 

11900 

2x 8090 18 

11200 

14300 

2x 8100 12 

12400 

14300 

2x 8125M.15 

15600 

18000 

2x 8150M.18 

18200 

21000 

2x 8175M.21 

20100 

21500 

2x 8200M.24 

23300 

24000 

V1 =  min. airflow required through heat 

exchanger enclosure 

V2 =  min. airflow required without per-forated 

inlet plate 

 

Table 8b  

Minimum airflow requirements for 3 RHC 

units in series 

:

 

Model 

V1 

(m

³

/h) 

3x 8030 06 

5250 

3x 8045 09 

7850 

3x 8050 06 

8750 

3x 8060 12 

10500 

3x 8075 09 

13000 

3x 8075 15 

13000 

3x 8090 18 

15800 

3x 8100 09 

17000 

3x 8125M.15 

22000 

3x 8150M.18 

26000 

3x 8175M.21 

30000 

3x 8200M.24 

35000 

V1 =  min. airflow required through heat 

exchanger enclosure 

P.S.

 : no perforated air inlet plate required 

 

12.3  Pressure  loss  through  multiple  heating 

modules

 

 

12.3.1  The  charts  below  (figures  14)  indicate  the 

pressure  loss  over  the  heating  module 

versus the total air volume through the heat 

exchanger enclosure (see figure 4 and table 

2) 

 

The temperature rise as shown is for 100% 

heat output. 

Summary of Contents for RHC 8000 DJL

Page 1: ...ndler or as part of an air handling system These appliances meet the following EC Directives Dir 2009 142 EC GAD Dir 2004 108 EC EMC Dir 2006 95 EC LVD Dir 2006 42 EC MD annexe ll sub B Subject to mod...

Page 2: ...2 8200M 24 Are destined to be incorporated in other machines air handlers or to be combined with other machines air handling systems and are for this reason not entirely in compliance with the machine...

Page 3: ...ON 13 7 ELECTRICAL EQUIPMENT 14 8 COMBUSTION CIRCUIT RHC 8000 M RJL 14 9 COMBUSTION CIRCUIT RHC 8000 M DJL 17 10 PRESSURE DROP INFORMATION 20 11 HEATING SECTION WITH BY PASS CHANNELS 23 12 INSTALLATIO...

Page 4: ...apply to the models RHC 8000 M RJL DJL gas fired fan assisted warm air heaters 2 2 Models RHC 8000 M RJL are intended for use in appliances as outdoors roof top systems Models RHC 8000 M DJL are inte...

Page 5: ...s Figure 1 Side view Figure 1a RHC 8000 DJL RJL not 8125 8150 8175 8200 n 59014_01 Figure 1b RHC 8125M 8150M 8175M DJL RJL Figure 1c RHC 8200M DJL RJL n 59710_01 n 59706_01 a 1 Gas connection 2 Flue o...

Page 6: ...0710RHC8 JLNLEN 6 36 Figure 2 Top view Figure 2a RHC 8000 DJL RJL not 8125 8150 8175 8200 n 59014_02 Figure 2b RHC 8125M 8150M 8175M DJL RJL n 59710_02 Figure 2c RHC 8200M DJL RJL n 59706_02 a...

Page 7: ...B C Y A1 A2 D A1 A2 D 8030 06 531 66 100 1244 65 466 100 65 466 100 8045 09 741 50 160 1244 85 656 130 160 581 100 8050 06 531 66 100 1844 85 446 130 65 466 100 8060 12 950 125 175 1244 85 865 130 160...

Page 8: ...e view RHC 8200M DJL RJL Dimensions applicable to model RHC 8000M see fig 1b 1c 2b 2c 3b 3c RHC 8000 M DJL RJL Type A A1 A2 A3 A4 D 8125M 15 1272 183 1089 741 531 130 8150M 18 1481 183 1298 741 741 13...

Page 9: ...70 400 400 400 8090 18 1369 1299 1244 1170 400 400 400 8100 12 950 880 1844 1170 400 400 400 8125M 15 1272 1202 1844 1770 400 460 420 8150M 18 1481 1411 1844 1770 400 460 420 8175M 21 1691 1621 1844 1...

Page 10: ...8050 06 6200 7150 50 00 24 00 14 40 8060 12 7500 8750 60 50 28 60 17 10 8075 09 9300 10790 75 00 35 40 21 20 8075 15 9300 11900 74 98 35 27 35 27 8090 18 11200 14300 90 09 43 16 43 16 8100 12 12400 1...

Page 11: ...in figure 6 Example expected minimum inlet temperature 5 C minimum required temperature rise shown on the chart 13 K Table 3 indicates the heat output kW of the different models The maximum allowable...

Page 12: ...containing RHC 8000 M heating modules shall be so constructed that it is fully protected against the rigours of the environment in which it is intended to operate 5 1 2 When applied as an RJL roof top...

Page 13: ...under normal operating conditions Viewing ports may be necessary Ensure no flammable substances are in the immediate environment of the heating module 6 0 GAS CONNECTION RC or RC 1 Attention All RHC 8...

Page 14: ...ctric strain re CENELEC 289 c Function of all electrical components and securities and operational inspection d Heat input and test for good and clean combustion e Auxiliary equipment to be supplied a...

Page 15: ...not obstructed Make sure the installation of the combustion inlet grill is securely fixed The outlet combustion sealing ring dia 100 PN 06 22786 104 dia 130 PN 06 22786 134 must be installed in the f...

Page 16: ...RHC 8150M 322 225 1 405 2 RHC 8175M 322 225 1 405 2 RHC 8200M 322 580 1 minimum 2 maximum HOLE 112mm or 142mm REQUIRED TO RECEIVE SEALRING PN 06 22786 104 or 06 22786 134 HOLE 50mm or 67mm REQUIRED TO...

Page 17: ...be via strain relief bushings It is recommended that sealing is accomplished by the use of the sealed ring type Connections between the burner module controls compartment must be effectively sealed fr...

Page 18: ...sure within the compartment remains neutral 9 1 8 A viewing port for the purpose of ascertaining the operation of the burner should be included The viewing port may be located behind a door or panel p...

Page 19: ...ES WITHIN THE COMBUSTION CIRCUIT 1 Combustion air inlet pipe 2 Flue outlet pipe 3 Teflon sealing ring 4 90 bend 5 Gas passage grommet vinly Rc or Rc 1 PN 06 22783 125 or 06 22783 054 Not delivered wit...

Page 20: ...0 PRESSURE LOSS THROUGH HEATING MODULE 10 1 The charts below indicate the pressure drop over the heating module versus the air flow volume through the heat exchanger enclosure see fig 4 and table 2 1...

Page 21: ...6 17 18 19 20 21 22 23 25 27 T T 20100 m h 23300 m h 21500 m h 24000 m h 11 12 13 14 15 16 17 18 19 20 21 22 23 25 27 29 Pressure loss through a single RHC8000 module 9300 m h 11900 m h 11200 m h 1430...

Page 22: ...12 13 14 15 16 17 18 19 20 21 22 23 24 24 23 22 21 20 19 18 17 16 15 14 13 12 11 T T 15600 m h 18200 m h 18000 m h 21000 m h Pre ss ure loss e s through RHC8000M m odule 0 25 50 75 100 125 150 175 16...

Page 23: ...8000M models 11 2 1 This calculation is applicable for total airflow conditions above V2 table 7 11 2 2 Consequently the perforated inlet plate must NOT be installed and must not be applied in combina...

Page 24: ...s x1 Recommended by pass dim A or C as calculated in section 11 1 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explained above the air flow VHS...

Page 25: ...0710RHC8 JLNLEN 25 36 Figure 13a Figure 13b FRONT VIEW SIDE VIEW...

Page 26: ...2 2 Maximum airflow through heat exchanger enclosure The recommendations as described in section 4 1 2 are applicable for RHC units when installed in series Checking the possibility of condensation f...

Page 27: ...2x RHC8075 09 2x RHC8100 12 24 28 32 36 40 44 48 24 28 32 36 40 44 48 24 26 28 30 32 34 36 38 40 44 48 T 2xRHC8050 06 T 2xRHC8075 09 T 3xRHC8100 12 Pressure losses through 2 RHC8000 heating modules 3...

Page 28: ...9 28 27 26 25 24 23 38 36 34 33 32 31 30 29 28 27 26 25 24 23 40 42 44 46 48 T 2x T 2x 15600 m h 18200 m h 18000 m h 21000 m h Pressure losses through 2 RHC 8000 heating modules in series 9300 m h 119...

Page 29: ...38 36 51 49 47 45 43 41 39 37 T 3xRHC8050 06 T 3xRHC8075 09 T 3xRHC8100 12 Figure 14e PRESSURE DROP FOR 3 UNITS IN SERIES Figure 14f Pressure losses through 2 RHC8000M in series 0 50 100 150 200 250...

Page 30: ...2 50 48 46 44 42 40 38 36 50 48 46 44 42 40 38 36 50 48 46 44 42 40 38 36 T 3xRHC8030 06 T 3xRHC8045 09 T 3xRHC8060 12 Pressure losses through 3 RHC 8000 heating modules in series 13000 m h 15800 m h...

Page 31: ...0 36000 38000 40000 42000 44000 46000 48000 50000 52000 Airflow m h through heat exchanger enclosure Pressure loss Pa 3x RHC8125M 15 3x RHC8150M 18 3x RHC8175M 21 3x RHC8200M 24 34 36 38 40 42 44 46 4...

Page 32: ...ximum by pass dimensions for a given air flow Vtot can be calculated as follows Vtot is the air flow expressed in m s FOR 2 UNITS IN SERIES a By pass besides heat exchanger Model dim B mm factor R1 fa...

Page 33: ...lated in section 11 1 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explained above the air flow VHS through the heat exchanger enclosure must be...

Page 34: ...properly install on the collar of the combustion ventilator outlet a pipe with dia 130mm and 200mm length and a 45 elbow both made of thick wall aluminium now unit 2 is ready for mounting the vertica...

Page 35: ...40 74 98 10 14 6 43 0 282 35 27 35 27 8090 18 109 88 99 00 90 09 12 16 7 72 0 282 43 16 43 16 8100 12 120 00 108 40 100 00 13 32 8 57 0 153 46 60 28 00 Gas rate 3 Heat input Heat output G25 G31 Power...

Page 36: ...00 300 2x 10 10 8150M 18 18 3 00 300 2x 10 90 8175M 21 21 3 00 300 2x 11 60 8200M 24 24 3 00 300 2x 12 00 Table 11 Injector size and burner pressure G31 propane inlet pressure 30mbar Injector size Mod...

Reviews: