28
5.0 Fault finding
Gas Supply ON
Burner fails
to light
Turn on Gas
Supply
Electric Supply
ON
Turn on Electric
Supply
Air in Gas
Supply
Purge Gas Line
Thermostat
calling for heat
Limit thermostat
operated
Reset Limit
thermostat
Air pressure
switch made
Check flue fan
connections
Flue fan running
Replace flue fan
Check flue is
clear
Change air
pressure switch
Spark ignition
on
Check HT leads
& connections
No flame
Faulty control
box
Change gas
valve
Faulty Gas
valve
Yes
Check fuse.
Replace if required
Yes
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes