background image

Form 433-CV/LN, Page 16

MAINTENANCE AND SERVICE

WARNING: If you turn off the power supply, turn off the gas. See Hazard Levels, page 1.

The material contained in the MAINTENANCE AND SERVICE Section of this manual is designed to aid a qualified service person in maintaining
and servicing this equipment. This unit will operate with a minimum of maintenance. To ensure long life and satisfactory performance, a heater that
is operated under normal conditions should be inspected and cleaned at the start of each heating season. If the heater is operating in an area where
an unusual amount of dust or soot or other impurities are present in the air, more frequent maintenance is recommended.

When any service is completed, be careful to reassemble correctly to ensure that no unsafe conditions are created. When re-lighting, always follow
the lighting instructions on the heater.

WARNING: Excessive dirt buildup on and inside the burner ports could cause fuel gas to spill out of
the back of the burner tube causing gas odor inside the building. If uncorrected, fuel spilling out of the
back of the burner tube could cause a fire or explosion. To prevent fuel gas from spilling from the back
of the burners, clean the burner ports at least annually.

Maintenance Schedule - The following procedures should be carried out at least annually (See Figure 11 and Paragraphs 20-30.):

Clean all dirt and grease from the primary and secondary combustion air openings (vents in cabinet panels).

Clean the fan blade, fan guard, and motor.

Clean the heat exchanger both internally and externally.

Check the burners for scale, dust, or lint accumulation.

Check the vent system for soundness. Replace any parts that do not appear sound.

Check the wiring for any damaged wire. Replace damaged wiring. (See Paragraph 13 for replacement wiring requirements.)

NOTE: Use only factory-authorized replacement parts.

CGA B149.1and B149.2, Installation Code for Gas Burning Appli-
ances and Equipment, and this manual. Determine that there is no
blockage or restriction, leakage, corrosion and other deficiencies
which could cause an unsafe condition.

3. In so far as practical, close all building doors and windows and all

doors between the space where the heater is and other spaces of the
building. Turn on clothes dryers and exhaust fans, such as range
hoods and bathroom exhausts, so they shall operate at maximum
speed. Do not operate a summer exhaust fan. Close fireplace damp-
ers.

4. Light the heater following the lighting instructions. Adjust the ther-

mostat for continued operation. Verify that combustion products

DANGER: The gas burner in this gas-fired equipment is designed and equipped to provide safe and
economically controlled complete combustion. However, if the installation does not permit the burner
to receive the proper supply of combustion air, complete combustion may not occur. The result is
incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death. Safe
operation of indirect-fired gas burning equipment requires a properly operating vent system which
vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL
RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR
DEATH.

Always comply with the combustion air requirements in the installation codes and in Paragraphs 7 and
8. Combustion air at the burner should be regulated only by manufacturer-provided equipment. NEVER
RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO ANY HEATER.
Indoor units installed in a confined space must be supplied with air for combustion as required by
Code and in Paragraph 8 of this heater installation manual. MAINTAIN THE VENT SYSTEM IN
STRUCTURALLY SOUND AND PROPERLY OPERATING CONDITION.

19. Check Installation & Start-up (cont'd)

Check the installation after start-up (cont'd):

are venting properly.  After determining that the heater vents prop-
erly, return doors, windows, exhaust fans, and fireplace dampers to
their previous  conditions. If improper venting is observed, the vent-
ing system must be corrected.

o

With the unit in operation, measure manifold gas pressure. See Para-
graph 12.

o

Turn the unit off and on, pausing two minutes between each cycle.
Observe for smooth ignition.

o

Place the "Owner's Envelope" containing the Limited Warranty, this
booklet, and any control or optional information in an accessible
location near the heater. Follow the instructions on the envelope.

Summary of Contents for FT30-CV

Page 1: ...ath Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment HAZARD INTENSITY LEVELS 1 DANGER Failure to comply will result in severe perso...

Page 2: ...and movable scaffold ing In addition the heaters must be located so as to be accessible for servicing adjustment etc 2 Warranty Refer to the limited warranty information on the Warranty Card in the O...

Page 3: ...and 45 inches mm Top 1 25 Flue Connector 6 152 Access Panel 18 457 Non Access Side 1 25 Bottom 1 25 Rear 18 457 Units must be installed so that the clearances in the table are provided for combustion...

Page 4: ...ll the assem bly so that the louvers will direct the air downward with the heater in its new position 3 Turn the access panel so that the labels are in an upright position Re attach the panel 10 Suspe...

Page 5: ...n venting Common Venting Terms and Requirements Common vents must be vertical The common vertical portion may be either a Type B double wall vent a masonry chimney lined with a Type B or listed liner...

Page 6: ...horizontal length is 6 ft 1 8M Vent Connector of another Category I appliance H R1 R2 Category I Appliance water heater Model FT CV or LN Model FT CV or LN Maximum Length of the Vent Connector of Oth...

Page 7: ...103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257...

Page 8: ...8 257 299 203 320 398 265 391 511 339 528 637 413 1 N A N A 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 N A N A 34 83 94 62 121 150 97 185 230 138 246 314 189...

Page 9: ...776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 9...

Page 10: ...N A N A 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1090 466 610 1386 597 1 N A N A 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1181 444 560 1537 580 2 N A N A...

Page 11: ...in Do not rely on the heater for support of either horizontal or vertical vent pipe n Vent Terminal The vent terminal should be a minimum of six feet from adjoining buildings The vent terminal should...

Page 12: ...40 24 84 51 160 98 320 195 490 299 930 567 100 38 23 79 48 150 92 305 186 460 281 870 531 125 34 21 72 44 130 79 275 168 410 250 780 476 150 31 19 64 39 120 73 250 153 380 232 710 433 175 28 17 59 36...

Page 13: ...fan motor remains energized for an additional 180 seconds NOTE This is a three trial system should the unit not sense burner flame the unit will lockout for one hour before initiating another trial f...

Page 14: ...CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS ARE FI...

Page 15: ...r natural or propane gas The burners are lightweight and factory mounted in an assembly which permits them to be removed as a unit for inspection or service vice technician to inspect the appliance an...

Page 16: ...r as practical close all building doors and windows and all doors between the space where the heater is and other spaces of the building Turn on clothes dryers and exhaust fans such as range hoods and...

Page 17: ...urner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explo sion hazard To prevent fuel gas spillin...

Page 18: ...a year Inspection should in clude all joints seams and the vent cap Replace any defective parts Flame Sensor Refer to Figure 10 and locate the flame sensor Dis connect the wire remove the screw and th...

Page 19: ...control at the thermostat or main power 6 Faulty combustion air proving switch 6 Replace combustion air proving switch 7 Main valve not operating 7 a Defective valve a If 24 volt is measured at the v...

Page 20: ..._______________________________________________________ __________________________________________________________________ __________________________________________________________________ Phone ____...

Reviews: