Programming Instructions for Wall Control Unit (WC100)
8
Normally there will be only one Wall Control Unit
connected to Control Board. Multi Wall Control Unit (up to
three) is also supported (see page 2). All Wall Control
Units will have the same priorities over each other. It
means that if multiple Wall Control Units command
Control Board differently, the latest command will be
executed by the Control Board. Each Wall Control Unit
has different address for communication purpose. The
addresses for Wall Control Units will be A1,A2, and A3.
The addresses can be set by entering into programming
mode (see page 7).
Switching between the HRV/ERV Operational Modes
%
OFF
Display after power up.
Mode OFF. Current humidity
70%
%
NORMAL
Press MODE button.
Mode changed to NORMAL.
HRV/ERV runs at
normal
airflow.
%
HIGH
Press MODE button.
Mode changed to HIGH
HRV/ERV runs in
High
Ventilation
airflow.
%
RECIRC
Press MODE button. Mode
changed to RECIRC. HRV/ERV
runs according to the sequence
for Recirculation mode.
%
ENER SAVE
Press MODE button. Mode
changed to ENER SAVE.
HRV/ERV runs according to the
sequence for
Energy Saving
mode
.
%
OFF
Press MODE button. Mode
changed to OFF. HRV/ERV
fans are
off
, no ventilation.
Note:
1. Factory programmed default mode: OFF
2. The Mode to be stored in the non-volatile memory (EEPROM),
so in case of power outage, the system to return in the last
selected mode.
a
Functions:
Adjusting Humidity Setpoint
%
OFF
Mode OFF. Current Humidity
70%
%
OFF
Humidity Mode can be disabled
by setting the Humidity setpoint
to 0%.
Humidity setpoint is between 0%
to 85% in 5% increment levels.
%
SET
Press or - button. The
Current Humidity setpoint is
displayed 75%.
%
Press + button. Humidity
setpoint is incremented.
SET
%
PROGRAM
Press + button. Humidity
setpoint is incremented.
SET
%
Press - button. Humidity
setpoint is decremented.
SET
%
OFF
Do not press any button for 10
sec. Display turns back to the
current Humidity 70%, OFF
mode. The Humidity setpoint has
been changed from 75 to 80%.
Note:
Factory programmed default humidity setting: 50%.
+
_
MODE
%
PROGRAM
NO BAL
TIMER
DEFR
SET
REMOTE
NORMAL
HIGH
RECIRC
ENER SAVE
OFF
All Available LCD
display electrodes
It is very important to program wall controller according to
HRV / ERV model, core type, CFM requirement etc. before
commissioning.
Now available with back light
for better viewing.