background image

                                                                                        

 

 

 

  

Revision 1.2D 

 

Page 11 of 17 

 

 

www.resourcedm.com 

ML Switch User Guide

 

 

Warning 

 
 
 
 
 
 

Please Note 

The specifications of the product detailed on this 
Set-Up  Guide  may change without notice. RDM 
Ltd. shall not be liable for errors or for incidental 
or consequential damages, directly and indirectly, 
in connection with the furnishing, performance or 
misuse of this product or document.

 

Ensure that all power is 
switched off before   
installing or maintaining 
this product 

EEV Control Operation 

 
Ensure the transducer is correctly connected and the jumper is in the Pressure position. 
 
Once  the  Switch  has  been  correctly  setup,  it  will  pass  values  to  each  of  the  controllers  connected  to  ports  1  through  10.  In  an  EEV 
application the evaporator in temperature probe reading for a case controller can be obtained from the ML Switch on which the controller 
is connected. A suction pressure transducer is connected from the case Island to the 4-20mA input of the ML Switch and the pressure 
read from this transducer is converted to a temperature based on the gas type being used by the system. This temperature is transmitted 
to each controller connected to the switch and along with the suction temperature probe local to the controller the superheat is calculated. 
Please  see  the  ML  Case  controller  user  document  from  the  RDM  website  for  further  details.  (P-15  Minimum  valve  opening)  We 
recommend that this parameter be set to 0% when using ML Pressure Hub to calculate Superheat. Please note that RDM recommended 
that the evaporator in temperature probe is fitted as the controller will use this to calculate the superheat in the event of a communication 
loss with the ML Switch. The ML Case controllers require to have P14 (Evaporator control) set to 1 (Remote) for this feature  to function 
correctly. 
 

 

 

Transducer Connection 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

MOP - Maximum Operating Pressure 

 

When the MOP alarm is created a valve off command is sent to the ML controllers connected to the ML Switch. The percentage that the 
valve shuts down to is dependent on the “Div Value” parameter in the ML case controller. When the ML Switch generates the MOP alarm 
the controller reduces the maximum valve opening to this percentage. For example if the Div Value” parameter is set to 50% and the 
MOP alarm is generated then the maximum valve opening will be limited to 50%. Therefore as the controller pulses the valve the 
maximum the valve will open to is 50%. 
 
If ML controllers are connected to the Switch then the LLV will be closed when the MOP alarm is created and return to normal operation 
when the alarm clears. When the pressure reduces below the MOP diff the valves will revert to normal operation at 1 minute intervals. 
The number of controller coming back to normal operation per minute depends on the “recovery count” value. 
 

 
 
 
 
 
 
 
 

 
 

+12V loop feed 

mA loop return 

mA input selector 

Summary of Contents for PR0109

Page 1: ...ML Switch User Guide Resource Data Management Ltd 80 Johnstone Avenue Hillington Industrial Estate Glasgow Scotland G52 4NZ UK 44 0 141 810 2828 Switchboard support resourcedm com Technical Support s...

Page 2: ...ID 5 PR0109 PHI USER GUIDE 6 ML Switch Type 6 Parameters 8 Parameters Description 9 Input Output table 10 EEV Control Operation 11 Transducer Connection 11 MOP Maximum Operating Pressure 11 Humidity C...

Page 3: ...connections for other network devices The Ethernet ports are self configuring for uplinks and standard 10 100 Base T device connections As well as the Switch function there is a 4 20mA input for addi...

Page 4: ...lers will not log on to network using pre 1 2 versions of ML Switch and IP Modules Controllers with the following label will only log on to network using ML Switch or ML IP Module with software versio...

Page 5: ...e 10 100 Base T ports are all self configuring Connection to a Data Manager Director Use a standard CAT5 patch lead and connect the Data Manager or Data Director to one of the three 10 Base T ports 10...

Page 6: ...and along with the suction temperature probe local to the controller the superheat is calculated Unlike the PR0109 Standard ML Switch version when this product is used with a Data Manager it is regis...

Page 7: ...ling or maintaining this product Click on Configure to set the type Then click Type Use the drop down selection to select the type required and then click Set Type Parameters can be configured using t...

Page 8: ...i 0 1 1 0 P 14 Evap 4 offset 0 0 to 0 5 0 to 7 2 0 1 Bar psi 0 1 1 0 P 15 Evap 5 offset 0 0 to 0 5 0 to 7 2 0 1 Bar psi 0 1 1 0 P 16 Evap 6 offset 0 0 to 0 5 0 to 7 2 0 1 Bar psi 0 1 1 0 P 17 Evap 7 o...

Page 9: ...2 Alarm Delay Delay before the HP alarm is generated P 33 HP Alarm If the pressure exceeds this value then a High Pressure alarm is generated once the alarm delay expires P 40 MOP If the pressure exce...

Page 10: ...p 8 Press 3 4 to 50 49 3 to 725 0 Bar psi I 10 Evap 9 Press 3 4 to 50 49 3 to 725 0 Bar psi I 11 Evap 10 Press 3 4 to 50 49 3 to 725 0 Bar psi I 12 Humidity 0 to 100 rH I 13 Sensor Temp 60 to 60 76 0...

Page 11: ...perheat Please note that RDM recommended that the evaporator in temperature probe is fitted as the controller will use this to calculate the superheat in the event of a communication loss with the ML...

Page 12: ...r GP timer channel directed to the ML Switch is in the on period the humidity control will operate as described above During the Data Manager GP timer channel off period the relay will pulse to the pr...

Page 13: ...ftware menu the up button is used to scroll up through the menu items Down Button When in the software menu the down button is used to scroll down through the menu items Button No function Network LED...

Page 14: ...tput States IO PArA View or change Parameters PArA ID View or change ID ID tyPE View or change Controller Type type nEt View or change the Network Settings Net SoFt View the Software version ESC Escap...

Page 15: ...Switch is in IP L mode a From the function menu scroll to select Id b The current id number will be shown Use the up down buttons to scroll through from 000 to 999 c Select the desired number and pre...

Page 16: ...can now view only the address given by the DHCP server To ease setup a single network mask length value is used If the address has been specified with a network mask value in dotted IP format e g 255...

Page 17: ...current protection device such as Fuse 1A 240 Vac Antisurge T HRC conforming to IEC 60127 Or MCB 1A 240 VAC Type C conforming to BS EN 60898 Mounting There is a fixing lug at each end of the Switch wi...

Reviews: