Before flushing the system

 

Î

Disconnect the expansion vessel from the solar thermal system. 

 

Î

Connect the pressure hose of the filling and flushing 
station to the fill valve (5) of the pump station.

 

Î

Connect the flushing hose of the filling and flushing 
station to the drain valve (3) of the pump station.

2.

 

Î

Close the ball valve of the pump station (4).

 

Î

Open the fill valve (5) and the drain valve (3). 

 

Î

Switch on the filling pump of the filling and flushing 
station.

 

Î

Flush the solar thermal system for at least 15 minutes by means of the filling 
and flushing station until the discharged solar fluid is free of gas bubbles and 
dirt particles.

 

Î

During  flushing,  vent  the  solar  thermal  system  several  times  until  the  dis-
charged solar fluid (e. g. Tyfocor

®

, see chap. 11) is free of air bubbles.

 

Î

Open the ball valve of the pump station (4). 

After flushing the system

 

Î

Connect the expansion vessel to the solar thermal system. 

 

Î

Close the drain valve (3) of the pump station while the filling pump is running. 

 

Î

Increase the system pressure (approx. 3,5 - 4 bar). 
The system pressure can be read from the pressure 
gauge.

 

Î

Close the fill valve (5).

 

Î

Switch off the filling pump.

BAR

 

Î

Check the pressure gauge to see whether the system pressure reduces and 
eliminate leaks where necessary.

 

Î

Slowly discharge the heat transfer fluid by means of the drain valve (3) until 
the operating pressure is set.

 

Î

Remove the hoses of the filling and flushing station and screw the caps onto 
the fill and drain valves. Manually start the solar thermal pump at maximum 
speed (see controller manual) and let the fluid circulate for at least 15 minutes.

 

Î

Vent the solar thermal system several times. 

 

Î

Check the system pressure at the pressure gauge.

 

Î

Check the antifreeze ratio (not required if a ready-
mix is used).

11.

%

Ball valve positions

WARNING!

Scald danger! Damage by overpressure!
When the ball valve is closed, too high pressure may occur in the 
blocked-off line if it is heated.

 

Î

In order to prevent scald danger and damage by 
overpressure, make sure the blocked-off line is not 
heated.

Ball valve in operating position, fluid flow in flow direction 
only

Ball valve open, fluid flow in both directions possible

Ball valve closed, no fluid flow

Draining the system

 

Î

Open the ball valve (4).

 

Î

Open the air vent at the highest point of the system (above the collectors).

 

Î

Open the drain valve (5).

Non-return valves

The non-return valves of the pump station are integrated into the ball valves in 
flow and return and have an opening pressure of 20 mbar.
In order to completely drain the system, the non-return valves have to be opened. 

 

Î

For this purpose, turn the handles of the ball valves by 45°.

 

Î

For normal system operation, open the ball valves completely.

Summary of Contents for FlowSol XL

Page 1: ...this RESOL product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully FlowSol XL www resol com Manual en Installation Operation Commissioni...

Page 2: ...trical works Initial installation must be effected by the system owner or qualified personnel named by the system owner Contents 1 Overview 3 2 Mounting the station 4 3 Flushing and filling the solar...

Page 3: ...m into account Ball valves in flow and return with non return valves and thermometer handles Non return valve Opening pressure 20 mbar openable Thermometer 0 160 C Connection to expansion vessel 1 ET...

Page 4: ...ing bracket Insert the flow and return lines into the wall mounting bracket and fasten them by means of the locking springs Connect the pipework between pump station and store and collector re spectiv...

Page 5: ...essary Slowly discharge the heat transfer fluid by means of the drain valve 3 until the operating pressure is set Remove the hoses of the filling and flushing station and screw the caps onto the fill...

Page 6: ...he union nut at the pressure side Now dismount the pump 10 Safety devices The pump station is equipped with a diaphragm safety valve which corresponds to the relavant directives and regulations For in...

Page 7: ...ing solar thermal and heating systems Its many thought out details facilitate transport operation and cleaning the attractive design makes it the ideal companion for a professional performance Heat tr...

Page 8: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Reviews: