4.11 Manual mode
Manual mode
Adjustment
channel
Description
Adjustment range / selection Factory setting
Stage 1
Manual mode selection for the
power unit, modulating
Auto, 0 … 100 %
(in steps of 10 %)
Auto
Fan
Manual mode selection for the fan On, Auto, Off
Auto
In the Manual mode menu, the operating mode of the power unit can be adjusted.
ATTENTION!
Damage through overheating!
The manual mode > 0 % of the power stage in a system electri-
cally connected, but not hydraulically filled can lead to damage
caused by overheating!
Î
Make sure the hydraulic system is filled and ready for
operation.
An operating mode can be selected for the power unit. The following options are
available:
Auto = Stage is in automatic mode
0 % = Stage is switched off
100 % = Stage is switched on at 100 %
The power of the modulating stage can be set to the manual mode in steps of 10 %.
Note:
After service and maintenance work, the relay mode must be set back to
Auto. Normal operation is not possible in manual mode.
4.12 User code
The access to some adjustment values can be restricted via a user code (customer).
1. Installer 0262 (Factory setting)
All menus and adjustment values are shown and all values can be altered.
If the installer user code is active, an E will be displayed next to the clock time.
2. Customer 0000
The installer level is not shown, adjustment values can be changed partly.
For safety reasons, the user code should generally be set to the customer code
before the controller is handed to the customer!
Î
In order to restrict the access, enter 0000 in the User code menu item.