GB
4
MU1H-1178GE23 R0320
6.2.3 Replace ball valve
1.
Close shut-off valve on inlet
2.
Release pressure on outlet side (e.g. through water
tap)
3.
Close shut-off valve on outlet
4.
Unscrew discharge connection
5.
Remove ball valve
6.
Screw in new ball valve
7.
Screw in discharge connection
8.
Slowly open shut-off valve on inlet
9.
Slowly open shut-off valve on outlet
7
Disposal
Observe the local requirements regarding correct waste
recycling/disposal!
8
Troubleshooting
9
Spare Parts
For Spare Parts visit homecomfort.resideo.com/europe
10 Accessories
For Accessories visit homecomfort.resideo.com/europe
Problem
Cause
Remedy
Too little or no water pressure
Shut-off valves upstream or downstream
from filter not fully open
Open the shut-off valves fully
Filter mesh dirty
Reverse rinsing
Filter is not fitted in flow direction
Fit filter in flow direction
Increased differential pressure between
inlet and outlet pressure gauge
Reverse rinsing interval is exceeded
Reverse rinsing
High degree of dirt in the water
Reverse rinsing
Decrease reverse rinsing interval
Replace filter sieve