GB
2
MU1H-1178GE23 R0320
1
Safety Guidelines
1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2
Technical Data
Note:
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be
proven individually.
3
Options
For Options visit homecomfort.resideo.com/europe
4
Assembly
4.1 Installation Guidelines
•
Install in horizontal pipework with filter bowl
downwards
– This position ensures optimum filter efficiency
•
Install shut-off valves
•
These filters are armatures which need to be
maintained regularly
•
Ensure good access
– Pressure gauge can be read off easily
– Simplifies maintenance and inspection
•
The installation location should be protected against
frost
•
Related to the EN 806-2 it is recommended to install
the filter immediately after the water meter
•
In order to avoid flooding, it is recommended to
arrange a permanent, professionally dimensioned
wastewater connection
4.2 Assembly instructions
1.
Thoroughly flush pipework
2.
Install filter
• Note flow direction
• Install without tension or bending stresses
3.
Seal in pressure gauges
4.
Install discharge connection
4.3 Discharge of reverse rinsing water
CAUTION!
According to EN1717 the space between bottom
from discharge connection at the filter and the
sewage piping (e.g. drain connection with syphon)
has to be 56mm at least.
To do this there are 3 options:
1.
Discharge into floor drain
2.
Drain into open container.
3.
Discharge into drain connector with syphon (min.
DN70)
*at 4 bar inlet pressure and 22 s reverse rinsing duration -
operated by actuator or at 4 bar inlet pressure and 3x 3 s
rinsing duration - operated by hand.
5
Operation
CAUTION!
Filter may only be operated with installed discharge
connection.
5.1 Reverse rinsing
At the latest every 6 months, reverse rinsing should be carried
out according to EN 806-5. Our recommendation at least
every 2 months.
Red pointer integrated into the view window of one of
the pressure gauges for setting the next reverse
rinsing
Media
Medium: Drinking
water
Connections/Sizes
Flange connection
PN16 acc. to EN 1092-2
Single filter:
DN65 - DN100
DN125 with 2 extension
flanges EXF125-A
2 filters parallel:
2 x DN80, 2 x DN100
Pressure values
Max. operating pressure:
1.5 - 16 bar
Nominal pressure:
PN16
Operating temperatures
Max. operating temperature
medium accord. to EN 1567:
30 °C
Max. operating temperature
medium:
65 °C (max. operating
pressure 6 bar)
Specifications
Installation position:
Horizontal, with filter bowl
downwards
Filter size
Reverse rinsing volume*
DN65 - 100
55 litre