![Rendamax R40 ECO Operating Manual Download Page 47](http://html.mh-extra.com/html/rendamax/r40-eco/r40-eco_operating-manual_1439802047.webp)
47
Water pressure
Screen display
Good
Read-out
Operation
status
Technical
read-out
Description
Action
FILL
dd 00:00
FILL
Bx12sc03
xx.x°C
P0,0
Water pressure is 0 bar,
boiler off
Top up water
FILL
dd 00:00
FILL
Bx12sc03
xx.x°C
P>0,7
Water pressure above
0.7 bar. The boiler is off.
The automatic venting
program starts
Top up water until
approx. 1,7 bar
Block.
dd 00:00
Vent
Prog.
xx.x°C
P>1,2
Automatic venting
program, afterwards
(approx. 13 min.) boiler is
on standby
Top up water until
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C
P>1,0 <4,0
Water pressure is good.
Boiler standby or in
normal operation
None
Block.
dd 00:00
xx.x°C
P>4,0
Water pressure too high,
boiler off due to blocking
Drain water until
approx. 1,7 bar
Good
dd 00:00
(variable)
xx.x°C
P<3,7
Water pressure is good.
Boiler operates normally
again
None
Message/
Block.
dd 00:00
FILL
Message
Mx24sc14
xx.x°C
P<1 >0,7
Water pressure too low.
Boiler is limited to 50%
load
Top up water until
approx. 1,7 bar
Menu structure at Basic level
Good
Operational status
Basic setting
Timeprog. options
Param Mode
Info
Tech. Read-out
CH prog
Set Date and time Boiler param
Cascade
DHW prog
Timeprog. CH
Other
Pump prg.
Timepr. DHW
Timepr. CH
Timep. DHW
CH temp
DHW temp
Units
Language
Restore Defaults
With the arrow buttons you can go
through the different chapters.
Press OK to select or to confirm a
change.
With the + and - button you can
increase or decrease a selected
value.
Back to previous screen or standard
read out: Press this ‘return-button’.
Remark: Depending which
parameter settings are set, some
options will not be displayed.
Menu structure
There are 2 setting levels
1. Basic level (manager/user):
Blue screen
2. Setting level (Installer):
Green screen
With the illumination switched off,
first press on one of the buttons to
switch the illumination on and then
continue with the setting. Having
pressed the last button, the blue
illumination will switch off after 2
min.
Refer to the Parameters chapter for all
parameters and related settings.
Commissioning
Menu structure at Basic level