Installation
Connections
Collective flue gas outlet over-pressure
An installation with a collective
flue gas outlet over-pressure in
combination with individually
controlled boilers (e.g. 0-10 V
control), where no bus cable
3905043 is connected, is NOT
allowed.
Diameter and venting lengths of the
flue gas outlet/air supply:
- Open system with over-pressure.
NOTE!
1. IPX0D at flue category B
23
and B
33
2. Only with bus cable 3905043
connected!
3. Adjust parameter 102 to 2
d
d
h
=d
=d
d
d
d
d
h
Diameter and venting lengths of the
flue gas outlet/air supply:
- Closed system with over-
pressure.
Please contact Rendamax.
Dimensions cascade flue R40 ECO
Open system, overpressure, parallel
Output (P) kW at 80/60°C
Type R40 ECO
d = minimum diameter Ø in mm
70
100
120
h = 2 - 5
h = 6 - 10
h = 11 - 15
h = 16 - 20
152
1
1
100
100
110
110
180
1
1
120
120
130
130
212
1
1
120
130
130
150
240
2
120
130
150
150
272
1
1
1
150
150
180
180
300
1
2
150
180
180
180
332
1
2
180
180
180
180
360
3
180
180
180
180
392
1
1
2
180
180
180
200
424
2
2
200
200
200
220
452
1
3
200
220
220
220
480
4
200
220
220
220
512
1
1
3
200
220
220
220
544
2
3
220
230
230
230
572
1
4
230
230
250
250
600
5
230
230
250
250
632
1
1
4
230
230
250
250
660
1
5
250
250
250
250
692
1
5
260
260
260
260
720
6
280
280
280
280
752
1
1
5
280
280
280
280
784
2
5
280
280
280
280
812
1
6
280
280
280
280
840
7
280
280
280
280
872
1
1
6
280
280
280
280
900
1
7
280
280
280
300
932
1
7
300
300
300
300
960
8
300
300
300
300