Point of emissions
Assessment level in accordance
with TA noise
days in dB(A)
nights in dB(A)
Industrial areas
70
70
Commercial areas
65
50
Core areas, village areas and mixed zones
60
45
General residential areas and small housing estates
55
40
Exclusively residential areas
50
35
Spa areas, hospitals and mental institutions
45
35
Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.
Definition of the Danger Area
WARNING!
Access to the unit is only permitted for author-
ised and trained persons. If unauthorised per-
sons can approach the danger areas, these
areas must be identified with corresponding
signs, barriers, etc.
n
The external danger area surrounds the equip-
ment up to a distance of 2 m, measured in all
directions from the unit housing.
n
The external danger area on-site can differ as
a result of the setup. The specialist company
performing the installation work bears the
responsibility for this.
n
The internal danger area is located inside the
machine and can only be reached with the use
of an appropriate tool. Access is prohibited for
unauthorised persons!
Minimum distances in mm for the outdoor modules
1
2
3
4
5
6
>= 250
>= 1500
>= 1500
>= 250
>= 250
>= 300
>= 600
>= 600
>= 250
>= 1500
>= 2000
Fig. 67: Minimum distances for installation of an outdoor module in mm
1: Against a wall, free flow air forward, backward
flow restriction
2: Against a wall, facing the wall air outlet, flow front
restriction
3: Freely between two walls, facing the wall outlet,
Sides: flow restrictions in front and rear
4: In a niche, free flow air to the front, rear and flow
restriction on both sides.
5: Before a covered wall, free flow air to the front,
rear and top of flow restrictions
6: Before a covered wall, air outlet towards wall,
flow restrictions behind and above
61