Electrical connection diagram
4. Feed both cables through the
edge protection rings on the
fixed connection panel.
5. Terminate the cables as shown
on the electrical connection
diagram.
6. Support the cable in the strain
relief and re-assemble the unit.
Proceed as follows to connect the
cable:
1. Remove the cover from the
unit.
2. Remove the side panel next to
the terminals.
3. Select the cable cross-section
according to the relevant
standards.
Connecting the outdoor component
Connection RXW 261-681
Connection RXD 260-680
Indoor unit
Outdoor
component
N
N
L
L
Neutral conductor
Phase conductor
N
L
Control conductor
3
3
Compressor
contactor
230 V~,
50 Hz,
L / N / PE
Mains cable
Earth conductor
PE
PE
PE
2
2
Reverse flow valve
1
1
Fan motor
Control conductor
Control conductor
Connection RXT 350
Indoor unit
Outdoor
component
N
N
L
L
Neutral conductor
Phase conductor
N
L1
Control conductor
Y
3
Compressor
contactor
230 V~,
50 Hz,
L1 / N / PE
Mains cable
Earth conductor
PE
PE
PE
O
2
Reverse flow valve
W
2
1
Fan motor
Control conductor
Control conductor
Neutral conductor
Phase conductor
Earth conductor
Defrost sensor Outdoor component
should be fitted on the pipe bend in
the lower third of the liquefier.
230 V~,
50 Hz,
L1 / N / PE
Control conductor
Compressor contactor
Reverse flow valve
Control conductor
Control conductor
Fan motor
3
2
1
O
O
O
O
Indoor unit
Outdoor
component
Mains cable
Indoor unit
Outdoor
component
N
N
L
L
Neutral conductor
Phase conductor
N
L
Control conductor
C
3
Compressor
contactor
400 V~,
50 Hz,
L1 / L2 / L3 / N / PE
Mains cable
Earth conductor
PE
PE
PE
V
2
Reverse flow valve
F
1
Fan motor
Control conductor
Control conductor
Fit the defrost sensor for the indoor
unit on the pipe bend in the lower
third of the liquefier.
Low pressure sensor
in outdoor component
LP
LP
LP
LP
P
O
O
O
O
HP
HP
HP
HP
P
High pressure sensor
in outdoor component
Connection RXD 1200
Connection RXT 520-680
Indoor unit
Outdoor
component
C
N
L
R
Neutral conductor
Phase conductor
N
L1
Control conductor
Y
3
Compressor
contactor
230 V~,
50 Hz,
L1 / N / PE
Mains cable
Earth conductor
PE
PE
PE
O
2
Reverse flow valve
W
2
1
Fan motor
Control conductor
Control conductor
REMKO RXS H
14