Add refrigerant
The unit contains a basic quantity of refrigerant. Additional refrigerant
may be required depending on the indoor unit used.
The revised refrigerant quantities are given in the following table:
Note that the employed
refrigerant is always filled in
liquid form!
CAUTION
Commissioning
The system can be commissioned
once all the components have
been connected and tested.
A functional check should be
performed to verify its correct
function and identify any unusual
operational behaviour prior to
handing it over to the operator.
This check is dependent on the
installed indoor unit.
The procedures are specified in the
manual for the indoor unit being
commissioned.
Function test and test run
Check the following points:
■
Leak tightness of refrigerant
pipes.
■
Compressor and fan running
smoothly.
■
In cooling mode, cold air should
be output by the indoor unit,
and warm air should be output
by the outdoor component.
RXS 261H RXS 351H RXS 521H RXS 681H RXS 1200H
RXW 261
+ 0 g
-
-
-
-
RXW 351
-
+ 0 g
-
-
-
RXW 521
-
-
+ 0 g
-
-
RXW 681
-
-
-
+ 0 g
-
RXD 260
+ 200 g
-
-
-
-
RXD 350
-
+ 200 g
-
-
-
RXD 520
-
-
+ 200 g
-
-
RXD 680
-
-
-
+ 200 g
-
RXD 1200
-
-
-
-
+ 0 g
RXT 350
-
+ 150 g
-
-
-
RXT 520
-
-
+ 150 g
-
-
RXT 680
-
-
-
+ 150 g
-
Cooling / heating
In addition, an additional amount of refrigerant must be added for
refrigerant pipe lengths exceeding 5 meters per circuit. Refer to the
following chart:
RXS 261H RXS 351H RXS 521H RXS 681H RXS 1200H
Basic pipe length
Additional fill quantity
Up to and incl. 5 m
0 g/m
0 g/m
0 g/m
0 g/m
0 g/m
5 m to max. 25 m
25 g/m
25 g/m
25 g/m
45 g/m
65 g/m
NOTE
Check the overheating to
determine the refrigerant fill
quantity
Wear protective clothing when
handling refrigerant.
CAUTION
Commissioning should only be
performed by specially trained
personnel and documented
after the certificate has been
issued.
Observe the manuals
for the indoor unit and
outdoor component when
commissioning the entire
system.
NOTE
REMKO RXS H
16