background image

Position of the air outlet plate fins 

The plate fins can be positioned in accordance with the 
following illustrations. 
The illustration below shows the plate fins when they 
are closed. 

Closed plate fins 

When the plate fins are completely open, the stream of 
air is blown in a downwards direction. 

This setting is unfavourable for cooling mode because it 
creates drafts. In winter, this plate fin position can be 
used to regain warm air on the ceiling of the room. 

Stream of air going downwards 

In cooling mode, the plate fins should be in a “half open” 
position (see figure below) or the oscillating mode 
should be selected.

 

Stream of air to the ceiling 

The air distribution can be changed by pressing the but-
ton (13)      . 
The line on the display indicates the position of the plate 
fins. 
If the distribution is to be set to oscillating, the corre-
sponding symbol must be visible on the display after 
pressing the button (13)      several times. 

The air outlet plate fins are automatically 
set depending on the operating mode. 

There are six different positions that the air 
outlet plate fins can be set to. 

The air outlet plate fins are set for oscillat-
ing air distribution. 

Symbols on the display 

The positions and settings of the air outlet plate fins are 
represented by the following symbols

Air distribution button (13)     

 

The ceiling cassette has 4 air outlet openings to distrib-
ute the cooled air in the room. 

Customisation button (11)      and (12) 

 

Proceed as follows if you want to save a personal oper-
ating mode that can be called up at any time: 

1. When the remote control is switched on or off, press 

the button (11)      and hold it down for 5 seconds. 

The customisation symbol     begins to blink on the 
display.

 

2. Press the button (6)     and select the operating mode 

you want. 

3. Select the desired temperature by pressing the button

(8)      or (9)     . 

4. Select the fan speed with the button (10)      . 
5. Select the mode for the air direction plate fins with the 

button (13)      . 

6. To save, press the button (11)      after you have en-

tered all options . 

7. Exit customisation mode after completing entry by 

pressing one of the buttons                              again. 

8. If you want to change one or more of the saved pa-

rameters, begin again with Step 1. 

9. Activate all selected and saved functions by pressing 

the button (12)     regardless of which operating mode 
the unit is in. 

 

 

Air outlet plate fins 

Air outlet plate fins 

Summary of Contents for RKV 13 C

Page 1: ...REMKO powerful like a bear REMKO RKV 13 C 18 C 24 C Ceiling Cassettes Edition GB P05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...sonnel 16 Installation 17 Condensation Connection 19 Electrical Connection 19 Two Room and Fresh Air Connection 21 Prior to Initial Operation 22 Initial Operation 22 Certification for Initial Operatio...

Page 4: ...indoor unit and the remote control from moisture Protect all electric cables and connection lines from being damaged for example by animals Protect the air conditioning unit and the remote con trol fr...

Page 5: ...at the polarity is correct when inserting the batteries Use the labelling in the slot Close the battery slot again Once the reset button 20 see page 12 is pressed the remote control is ready for opera...

Page 6: ...sor of the fan is defective or outside of its regu lation range Blinks 4 times The frost protection mechanism has been activated Blinks 10 times EEPROM defective Green light ON OFF signal It lights up...

Page 7: ...he unit does not switch off this process must be re peated Switching the unit on Button 7 If the air conditioning unit is to be switched on only the clock may be visible on the remote control display...

Page 8: ...mbol appears on the display M Cooling mode In this operating mode the room in the air is cooled and slightly dehumidified The following section Temperature selection buttons describes how to set the d...

Page 9: ...late fins can be set to The air outlet plate fins are set for oscillat ing air distribution Symbols on the display The positions and settings of the air outlet plate fins are represented by the follow...

Page 10: ...orresponding symbol disappears from the dis play 3 Remember if the unit is already switched on it is only possible to program another start up time The current settings of the unit are transferred for...

Page 11: ...s 5 Press the button 6 repeatedly until UCFG ap pears on the display 6 Press either the button 8 or 9 to change the preset from heating pump HP to air conditioning unit AC 7 Press the button 13 to tra...

Page 12: ...and then press the 7 button to quit the configuration menu G If no button is pressed for 30 seconds the configu ration menu is automatically exited and program ming must be started from the beginning...

Page 13: ...e to the bottom Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all units and send it back...

Page 14: ...ia control line outdoor part Power consumption W 75 80 105 Current consumption A 0 4 0 4 0 5 Fan capacity W 63 68 93 Fan speeds 3 automatic 3 automatic 3 automatic Air volume current per speed m h 550...

Page 15: ...hade Electromagnetic fields are disrupt ing transmission Does the unit work when devices in the vicinity are switched off No signal transmission when sources of disruption are operated simultaneously...

Page 16: ...bjects that emit intense heat e g lights Install it in the middle of the room instead Wall lead throughs Wall lead throughs are necessary to establish the con nection between the indoor unit and the o...

Page 17: ...on mount and the bottom of the intermedi ate ceiling see figure above Connect the refrigerant control and condensation lines to the indoor unit as described below and check again hat the unit is posit...

Page 18: ...t is conducted using dry nitrogen The connections that have been established are sprayed with a leak locator spray to test for imperme ability If bubbles appear the connection was not made properly Ti...

Page 19: ...door unit the system must be cur rent free The electrical connections of the indoor unit and the ter minals of the control line to the outdoor part are located on the regulating panel The regulating p...

Page 20: ...utral conduct External conduct No function Protection conduct Wiring diagram RKV 13 C Main board Fan motor Micro float regulator Condensation pump LED IR connection Plate fin motor and micro plate fin...

Page 21: ...nit To do this use a black strip with ad hesive on one side which is stuck to the opening s to be sealed The strip must be able to withstand the strain from the air pressure permanently The flanged co...

Page 22: ...indicate operation 3 Connect the unit to the power supply and switch the power on 4 Press down the buttons 9 and 13 of the re mote control for five seconds The display is deleted The letters Src for a...

Page 23: ...re The following must be performed measured validated during initial operation Test Visible check setup assembly of outdoor part and indoor unit s OK problem Visible check of the heat exchanger OK pro...

Page 24: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Reviews: