background image

22 

Installing the air direction plate 

To provide cool fresh air to the room, it is necessary to 
mount the supplied air direction plate made of plastic.

 

Separating 

wall 

Air direction 

plate 

Frame 

Prior to Initial Operation

 

 

After the pressure check has been performed, the vac-
uum pump must be connected to the valve connections 
of the outdoor part by means of the manometer station 
and a vacuum created. 
Prior to initial operation of the unit and after contact with 
the cold cycle, the following checks must be performed 
and documented in the initial operation log: 

à

Check all refrigerant lines and shut-off valves for leaks 
with a leak locator spray or soapy water when the unit 
is off. 

à

Check that the connection lines did not get switched 
by mistake.          

Especially for the RKM series 600 and 700.

 

à

Check the refrigerant lines and the insulation for 
damage. 

à

Check that the electrical connection between the in-
door unit and the outdoor part is correct. 

à

Check all fixtures and suspended parts to ensure that 
they are in the proper position and at the correct 
height. 

à

If the refrigerant line is longer than 5 m, more refriger-
ant should be added to the system. 

G

 

To put the unit back into operation after a power 
outage, it must be completely unplugged from the 
power supply first!

 

The air direction plate is positioned as shown above. 

à

In the “Test” operating mode, “Room temperature 
regulation“ and “Cooling mechanism start protection“ 
are not activated.          

The green, red and yellow lights on the receiver of 
the indoor unit blink to indicate operation.

 

3.  Connect the unit to the power supply and switch the 

power on. 

4.  Press down the buttons (9)      and (13)     of the re-

mote control for five seconds  

The display is deleted. The letters “Src“ for a service 
test appear on the time display.

 

5.   After the test is complete, press the button (7)      to 

exit test mode. 

6.   Remember: if no button is pressed for 30 minutes, 

the configuration menu is automatically exit and the 
process must be reinitiated. 

Initial Operation

 

 

The unit may only be put into operation by the manufac-
turer or an authorised representative. Initial operation 
must be performed using the certification of initial op-
eration (page 18) and documented. 
During the test run, check all regulating, control and 
safety mechanisms to ensure that they are functioning 
and set properly. 

1.  Switch the customer-installed main switch or fuse on. 
2. Adjust the target temperature on the indoor unit to a 

lower value than the existing room temperature us-
ing the remote control. 

3. Press the button 6       to activate cooling mode. 
4. The compressor starts a couple of minutes later due 

to the delayed start. 

5. Check the indoor unit’s control mechanisms using 

the functions described in the section “The remote 
control”. 

Timer, temperature settings, fan mode and dehu-
midifying mode

6. Familiarise the operator with the system and give 

him the certification for initial operation. 

Additional preparation 

After the unit has been completely connected and 
checked, the indoor unit, outdoor part and remote con-
trol must be prepared for operation. 
The operating test is conducted as follows: 
1.   Check all electrical connections.       

Follow instructions and wiring diagrams.

 

2.   Insert the batteries into the remote control but leave 

it switched off. 

Summary of Contents for RKV 13 C

Page 1: ...REMKO powerful like a bear REMKO RKV 13 C 18 C 24 C Ceiling Cassettes Edition GB P05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...sonnel 16 Installation 17 Condensation Connection 19 Electrical Connection 19 Two Room and Fresh Air Connection 21 Prior to Initial Operation 22 Initial Operation 22 Certification for Initial Operatio...

Page 4: ...indoor unit and the remote control from moisture Protect all electric cables and connection lines from being damaged for example by animals Protect the air conditioning unit and the remote con trol fr...

Page 5: ...at the polarity is correct when inserting the batteries Use the labelling in the slot Close the battery slot again Once the reset button 20 see page 12 is pressed the remote control is ready for opera...

Page 6: ...sor of the fan is defective or outside of its regu lation range Blinks 4 times The frost protection mechanism has been activated Blinks 10 times EEPROM defective Green light ON OFF signal It lights up...

Page 7: ...he unit does not switch off this process must be re peated Switching the unit on Button 7 If the air conditioning unit is to be switched on only the clock may be visible on the remote control display...

Page 8: ...mbol appears on the display M Cooling mode In this operating mode the room in the air is cooled and slightly dehumidified The following section Temperature selection buttons describes how to set the d...

Page 9: ...late fins can be set to The air outlet plate fins are set for oscillat ing air distribution Symbols on the display The positions and settings of the air outlet plate fins are represented by the follow...

Page 10: ...orresponding symbol disappears from the dis play 3 Remember if the unit is already switched on it is only possible to program another start up time The current settings of the unit are transferred for...

Page 11: ...s 5 Press the button 6 repeatedly until UCFG ap pears on the display 6 Press either the button 8 or 9 to change the preset from heating pump HP to air conditioning unit AC 7 Press the button 13 to tra...

Page 12: ...and then press the 7 button to quit the configuration menu G If no button is pressed for 30 seconds the configu ration menu is automatically exited and program ming must be started from the beginning...

Page 13: ...e to the bottom Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all units and send it back...

Page 14: ...ia control line outdoor part Power consumption W 75 80 105 Current consumption A 0 4 0 4 0 5 Fan capacity W 63 68 93 Fan speeds 3 automatic 3 automatic 3 automatic Air volume current per speed m h 550...

Page 15: ...hade Electromagnetic fields are disrupt ing transmission Does the unit work when devices in the vicinity are switched off No signal transmission when sources of disruption are operated simultaneously...

Page 16: ...bjects that emit intense heat e g lights Install it in the middle of the room instead Wall lead throughs Wall lead throughs are necessary to establish the con nection between the indoor unit and the o...

Page 17: ...on mount and the bottom of the intermedi ate ceiling see figure above Connect the refrigerant control and condensation lines to the indoor unit as described below and check again hat the unit is posit...

Page 18: ...t is conducted using dry nitrogen The connections that have been established are sprayed with a leak locator spray to test for imperme ability If bubbles appear the connection was not made properly Ti...

Page 19: ...door unit the system must be cur rent free The electrical connections of the indoor unit and the ter minals of the control line to the outdoor part are located on the regulating panel The regulating p...

Page 20: ...utral conduct External conduct No function Protection conduct Wiring diagram RKV 13 C Main board Fan motor Micro float regulator Condensation pump LED IR connection Plate fin motor and micro plate fin...

Page 21: ...nit To do this use a black strip with ad hesive on one side which is stuck to the opening s to be sealed The strip must be able to withstand the strain from the air pressure permanently The flanged co...

Page 22: ...indicate operation 3 Connect the unit to the power supply and switch the power on 4 Press down the buttons 9 and 13 of the re mote control for five seconds The display is deleted The letters Src for a...

Page 23: ...re The following must be performed measured validated during initial operation Test Visible check setup assembly of outdoor part and indoor unit s OK problem Visible check of the heat exchanger OK pro...

Page 24: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Reviews: