background image

REMKO MKT

7

With low cleaning effort, you 
can guarantee malfunction-free 
operation and a long service 
life.

■ 

Use only mild, environment-
friendly cleaning agents.

■ 

Regularly clean the  
ventilation slots. 

■ 

Clean the device as required, 
but at least once a year, with 
a moist cloth and lukewarm 
water. 

■ 

Do not expose the device to 
direct water spray. 

Maintenance and Care

Cleaning the air filter

Clean the air filter regularly, 
but at least every 100 operat-
ing hours. In case of strongly 
contaminated air, the period is 
reduced accordingly.

1. 

Switch off the device and 
pull the mains plug.

2. 

Remove the filter from the 
device (Fig. 14).

3. 

Clean the filter using a 
vacuum cleaner or, in case 
of heavy soiling, carefully 
using lukewarm water (Fig. 
15/16).

4. 

Let the filter air-dry and then 
reinsert it.

Fig. 14  

Removing the air filter 

upwards from the machine

CAUTION

Always turn off the device  
and pull the mains plug before 
cleaning!

Never operate the device 
without the air filter.

Fig. 15 /16 

Cleaning the air filter

Fig. 17  

Draining the condensate

Draining the condensate

■ 

The condensate evaporates 
during operation and is then 
conducted outside with the 
exhaust air via the air outlet 
hose. 

■ 

In case of extreme humidity, 
the device collects conden-
sate in a reservoir. If the 
permissible level is exceeded, 
the red fault LED lights up 
and the device shuts down. 

■ 

The reservoir must be  
emptied via the condensate 
drain spout (Fig. 17).

Fig. 13  

Functional principle of the cooling process

Functional principle of 
the cooling process

The air conditioner

 

cools the air by re

-

moving heat from it. 
The fan (circulation 
air) conducts cooled 
air into the room. The 
heat that the device 
has removed from the 
air is conducted out

-

side via the air outlet 
hose.

Ventilator 

 

(exhaust air)

Evaporator

Condenser

Cooling circuit

Air inlet (exhaust air)

Air inlet (circulation air) 

with air filter

Humidity is removed 
from the air and drips 
as condensate from the 
evaporator onto the hot 
condenser and evapora

-

tes. Excess condensate 
drips from the condenser 
into a collection tray 
and conducted from 
there to the condenser 
again using a rotor, 
evaporated, and then 
conducted away with 
the exhaust air flow.

Cooled circulation 

air in the room     

Fan (circulation air)

Warm exhaust air 

outside

Summary of Contents for MKT 250

Page 1: ...dify Mode Fan Mode Timer Functional Principle of the Cooling Process Maintenance and Care Cleaning the Filter Draining the Condensate Trouble Shooting Taking the Device Out of Service Warranty Environ...

Page 2: ...ains supply line Protect all electrical lines of the device from damage even from animals Select the extension lines of the mains supply line depending on the connected load of the device the line len...

Page 3: ...that the cooling effect can be maintained Observe the following notices Plug the air outlet hose in cluded in delivery onto the air outlet on the rear panel of the device Lock both catches on the air...

Page 4: ...splay 7 13 Green Set Temp LED 14 C F toggle button only on the remote control Operation The device is operated comfortably using the control panel on the device or the in frared remote control Keys wi...

Page 5: ...is pressed the display switches from the room temperature to the set tempera ture LED 13 lights up and shows the desired temperature for 15 seconds 7 Set the desired room temperature using the Timer T...

Page 6: ...ondensate Draining the condensate The condensate evaporates during operation and is then conducted outside with the exhaust air via the air outlet hose In case of extreme humidity the device collects...

Page 7: ...e and pull the mains plug 2 Place a flat tray under the condensate drain spout and remove the plug Fig 17 3 After the condensate has drained reinsert the plug firmly The device is not cooling properly...

Page 8: ...sign sub ject to alteration Control panel Evaporator fan Condenser Red Orange Yellow White Red Red Red Blue Blue Blue Blue Condenser Condenser Compressor Evaporator fan Reservoir motor Mains plug Whit...

Page 9: ...to the wall bushing To prevent cold bridges insulate the telescopic pipe with suitable insulating material Wall the telescopic pipe into the core hole in such a way that it is flush to both sides of t...

Page 10: ...O MKT 11 Fig 20 Device diagram of the MKT 250 Technical dimensions and design subject to alteration 28 31 29 30 17 18 25 19 20 15 24 32 22 8 10 9 5 16 7 6 21 4 13 14 11 26 27 12 23 1 2 3 33 Device Dia...

Page 11: ...824 15 Exhaust air pipe adapter 1106865 1106865 16 Condenser 1 5 F 1106866 1106866 17 Evaporator 1106894 1106894 18 Fan housing circulation air 1106822 1106822 19 Fan wheel circulation air 1106823 110...

Page 12: ...ume approx m 80 Temperature setting range C 16 up to 32 Temperature operating limits C r F 16 bis 35 35 bis 85 Refrigerant R 410A Operating pressure max cooling circle kPa 1900 2800 Refrigerant quanti...

Reviews: