DIP1:
Unit type
SW
1
SW
2
SW
3
SW
4
KWD 25EC
ON
OFF OFF OFF
KWD 35EC
ON
OFF OFF OFF
KWD 45EC
OFF
ON
OFF OFF
KWD 55EC
OFF OFF
ON
OFF
KWD 70EC
ON
OFF OFF OFF
KWD 85EC
ON
ON
OFF OFF
KWD 100EC
OFF OFF
ON
OFF
DIP3:
Function logic
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
2-conductor cooling/heating
OFF OFF OFF
2-conductor with electrical heating register (backup) OFF OFF
ON
2-conductor only cooling mode
OFF
ON
OFF
2-conductor with electrical heating register (1st stage) OFF
ON ON
4-conductor without electrical heating
register
ON ON
OFF
4-conductor with electrical heating register (backup)
ON ON ON
Use of a control valve
ON
Use without a control valve
OFF
Heating mode fan operation >36°C
ON
Heating mode fan operation >28°C
OFF
Close-loop fan operation
ON
Open-loop fan operation
OFF
Re-heat mode fan not active
ON
Re-heat mode fan active
OFF
Use of the internal controller
ON
Use of external controllers
OFF
Configuration
The units can also be adjusted
to requirements retroactively
by adjusting DIP switch blocks
1 to 3 accordingly.
DIP switch block 1 configures
unit-specific parameters and must
be set in accordance with the
table below. DIP switch block 2
configures the network addresses
within a bus and DIP switch block 3
configures the unit's functions.
Configuration is carried out using
white slide switch SW1-4 for DIP1,
SW1-6 for DIP2 and SW 1-8
for DIP3.
The following settings must be
made according to usage before
starting up for the first time.
Unit configuration (DIP1)
Adjusting this DIP switch provides
the controller with specific key
variables that are required
for safe control behaviour
and optimised unit operation.
Only the configuration specified
for the relevant unit is permitted
to be used here, as this is the
only way to guarantee optimised
control behaviour.
Network configuration (DIP2)
The addresses for the leading
(master) and subsequent (slave)
units are defined using switch
block DIP2.
Function logic (DIP3)
The units can be used
for numerous applications
and requirements. The following
settings are possible using switch
block DIP3:
SW 1-3: 2- or 4- conductor function
SW 4: Use of a valve
SW 5: Fan function
in the warm-up phase
SW 6: Fan communication
SW 7: Fan function in re-heat
mode
SW 8: internal/external controller
DIP switch blocks 1 to 3
DIP switch block 1
Switch SW1
Example:
SW1 to 6
on DIP2
Switch SW2
Switch SW3
Switch SW4
Switch SW5
Switch SW6
DIP switch block 2
DIP switch block 3
DIP2:
Network
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
Master
OFF OFF OFF OFF OFF
ON
Slave 1
OFF OFF OFF OFF OFF OFF
Slave 2
ON
OFF OFF OFF OFF OFF
Slave 3
OFF
ON
OFF OFF OFF OFF
Slave 4
ON ON
OFF OFF OFF OFF
Slave 5
OFF OFF
ON
OFF OFF OFF
Slave 6
ON
OFF
ON
OFF OFF OFF
Slave 7
OFF
ON ON
OFF OFF OFF
Slave 8
ON ON ON
OFF OFF OFF
Slave 9
OFF OFF OFF
ON
OFF OFF
Slave 10
ON
OFF OFF
ON
OFF OFF
Slave 11
OFF
ON
OFF
ON
OFF OFF
Slave 12
ON ON
OFF
ON
OFF OFF
Slave 13
OFF OFF
ON ON
OFF OFF
Slave 14
ON
OFF
ON ON
OFF OFF
Slave 15
OFF
ON ON ON
OFF OFF
Slave 16
ON ON ON ON
OFF OFF
Slave 17
OFF OFF OFF OFF
ON
OFF
Slave 18
ON
OFF OFF OFF
ON
OFF
Slave 19
OFF
ON
OFF OFF
ON
OFF
Slave 20
ON ON
OFF OFF
ON
OFF
Slave 21
OFF OFF
ON
OFF
ON
OFF
Slave 22
ON
OFF
ON
OFF
ON
OFF
Slave 23
OFF
ON ON
OFF
ON
OFF
Slave 24
ON ON ON
OFF
ON
OFF
Slave 25
OFF OFF OFF
ON ON
OFF
Slave 26
ON
OFF OFF
ON ON
OFF
Slave 27
OFF
ON
OFF
ON ON
OFF
Slave 28
ON ON
OFF
ON ON
OFF
Slave 29
OFF OFF
ON ON ON
OFF
Slave 30
ON
OFF
ON ON ON
OFF
Slave 31
OFF
ON ON ON ON
OFF
Slave 32
ON ON ON ON ON
OFF
REMKO KWD EC series
28