Electrical wiring
■
We recommend installing
a master / repair switch
provided by the customer
close to the indoor unit.
■
The power supply is made
at the indoor unit, a control line
to the chiller is not necessary.
■
If a condensate pump, which
is available as an accessory,
is used in conjunction with
the unit, the pump switch-off
contact switches off the power
supply or the valve if necessary.
■
The terminal block is located
inside the unit. It can be
accessed after opening
the cover.
Proceed as follows to connect:
1. Open the control box cover
by removing the fixing screws
and lifting off the cover.
2. Feed the de-energised cable
through the edge protection
rings on the control box
and clamp the cable
in the strain relief.
3. Then connect the cable
in accordance with the
connection diagram.
4. Connect the electrical plugs
on the cover to the mating
connectors on the cassette.
It is not possible to incorrectly
connect these.
5. Configure the unit according
to its use via the switch blocks
and the terminal connections.
6. Install all removed parts.
All electrical installation work
is to be performed by specialist
companies. Disconnect the
power supply when connecting
the electrical terminals.
CAUTION
Control box cover
KWD 25 EC to 100 EC
Check all plug and terminal
connections to verify
that they are tight and make
a permanent contact. Tighten
as required.
CAUTION
KWD 25 EC to 100 EC control box
Measurement
temperature
C°
Probe
resistance value
-20
37.4 k
Ω
-15
29.0 k
Ω
-10
22.7 k
Ω
-5
17.9 k
Ω
0
14.2 k
Ω
+5
11.4
Ω
+10
9.1 k
Ω
+15
7.4 k
Ω
+20
6.1 k
Ω
+25
5.0 k
Ω
+30
4.1 k
Ω
+35
3.4 k
Ω
+40
2.9 k
Ω
+45
2.4 k
Ω
+50
2.0 k
Ω
+55
1.7 k
Ω
+60
1.5 k
Ω
+65
1.3 k
Ω
+70
1.1 k
Ω
+75
0.9 k
Ω
REMKO KWD EC series