ID
Description
Desig.
Details
ID6115
Low pressure differ-
ence
The pressure difference is too low to start the com-
pressor
ID6116
Maximum defrosting
period
Maximum defrosting period
Error
ID
Description
Desig.
Details
ID7050
Anti-freeze protection
The anti-freeze protection in the heat pump's heat
exchanger was triggered due to an inlet temperature
that is too low. After rectifying the cause of the error,
reset the error in (Expert/Settings/Heat pump/Basic set-
tings) and, if necessary, de-energise the outdoor unit.
ID7103
Incorrect phase
sequence (rotating
field)
µ
PC
Please check the phase sequence (the rotating field) of
the power supply
ID7108
The anti-freeze protec-
tion
In the heat pump's heat exchanger was triggered due to
a return temperature that is too low. After rectifying the
cause of the error, reset the error in (Expert/Settings/
Heat pump/Basic settings) and, if necessary, de-ener-
gise the outdoor unit.
ID7150
EEV motor fault
µ
PC
EEV motor fault. Please contact an authorised service
technician
ID7200
Open contact - storage
tank 1 bottom probe
S02
Open contact - storage tank 1 bottom probe
ID7201
Short circuit - storage
tank 1 bottom probe
S02
Short circuit - storage tank 1 bottom probe
ID7202
Open contact - storage
tank 1 middle probe
S09
Open contact - storage tank 1 middle probe
ID7203
Short circuit - storage
tank 1 middle probe
S09
Short circuit - storage tank 1 middle probe
ID7204
Open contact - storage
tank 1 top probe
S08
Open contact - storage tank 1 top probe
ID7205
Short circuit - storage
tank 1 top probe
S08
Short circuit - storage tank 1 top probe
ID7206
Open contact - external
probe
S10
Open contact - external probe
ID7207
Short circuit -
external probe
S10
Short circuit - external probe
ID7208
Open contact -
refrigerant probe
S07
Open contact - refrigerant probe
ID7209
Short circuit - refrig-
erant probe
S07
Short circuit - refrigerant probe
ID7210
Open contact - circula-
tion temp. probe
S05
Open contact - drinking water circulation temperature
probe
REMKO Smart-Control