REMKO GPM
PARAM
K
TSP
Factory
setting
Standard
Description
1
A1
0
0 - 100
Minimum modulation value
2
A2
0
0 - 100
Maximum modulation value
3
A3
70
20 - 100
Starting output
4
A4
20
0 - 255
Value of the integral factor
5
A5
10
1 - 100
Value of the proportional factor
6
A11
25
25 - 255
Stabilisation time of the flame
7
A17
4
0 - 4
Number of automatic resets after fault F1
8
A28
50
0 - 100
Percentage of OUT3 activation
9
A34
10
10 - 95
REG SAN minimum value
10
A35
0
0 - 1
Summer operation of the fan
11
C1
0
0 - 1
Room correction
12
C3
60
0 - 255
Delay time of the fan ON
13
C4
120
0 - 255
Delay time of the fan OFF
14
C5
0
0 - 1
Heating mode release
15
C8
0
0 - 1
Frost protection release
16
ST3
7.5
-5 + 30
Frost protection switchpoint temperature
17
A12
0
0 - 1
Release of external room sensor
18
A16
90
1 - 99
Correction coefficient
19
A24
1.5
1 - 20
Correction neutral range
20
A15
0
0 - 1
Selection of the PWM speed combination table
21
A31
2
2 - 3
Divisor for HALL message
REG SAN
ST1
21
10 - 95
Sensor NTC1 switchpoint
Control PCB parameter table