Fault P2: High pressure fault
Check the heat exchanger of the outdoor unit
and indoor unit. Are the heat exchangers
clean?
NO
Clean the heat exchangers.
YES
Are the corner shut-off valves open?
NO
Open corner shut-off valves
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
Fault P3: Refrigerant level low
Are the corner shut-off valves open?
NO
Clean the heat exchangers.
YES
Check the joints of the refrigerant circuit for
leaks. Are oily areas present?
YES
NO
Perform an overpressure leak test. Is the
cooling circuit tight?
NO
Rectify the leak. Adjust the refrigerant quan-
tity.
YES
Extract the refrigerant and check the refrig-
erant fill quantity. Refill the refrigerant to the
appropriate fill quantity.
Fault P4: Outdoor unit heat exchanger probe overtemperature
Check the heater exchanger of the outdoor
unit. Is the heat exchanger clean?
NO
Clean the heat exchangers.
YES
Is the fan motor working correctly?
NO
Check fan motor.
YES
Refrigerant cannot circulate. Possibly due to
internal contamination or kinked lines.
41