8
REMKO ATK
Connecting the units to
the electrical power supply
1. Move the operating
switch to the "0"
(Off) position.
2. Connect the power plug to a
properly installed
and appropriately
safeguarded
230 V/50 Hz
mains socket.
Commissioning
The units must be checked
for visible defects on the
operating and safety devices as
well as proper installation and
correct electrical wiring before
commissioning.
One person, who has been
adequately trained in the handling
of the units, must be tasked with
operation and monitoring of the
units.
■
The units must installed to be
stable in a horizontal position
■
Ensure there is an adequate
supply of combustion air
■
Check that the inlet and outlet
are free
■
Prevent overpressure and
underpressure in the installation
area
■
The fuel supply must be
ensured with suitable fuel
■
The fuel tank may only be filled
when the unit is switched off.
Do not use biodiesel!
■
Use only clean and suitable
tanks for filling
NOTE
The exhaust gas values must
be checked and/or adjusted
by authorised and qualified
technicians according to
the local conditions.
NOTE
The electrical connection for
the units must be made at a
separate feed point with a residual
current device in accordance with
VDE 0100, Section 55.
NOTE
Only suitable and clean fuels
may be used.
ATTENTION
In the event of defects that
endanger the operational
safety of the units, operation
of the units must be
discontinued immediately and
the supervisor informed!
ATTENTION
In this operating mode,
the fuel tank must always be
filled with a basic quantity of
heating oil.
There is no warranty claim
for pump damage due to dry
running!
NOTE
Paraffin formation can start
at temperatures below 5°C.
To avoid this appropriate
preventative measures must
be implemented, e.g. winter
Diesel.
Ventilation only operation
In this switch position, the supply
air fan runs permanently.
The units can be used for air
recirculation or ventilation
purposes.
1. Check the content of the fuel
tank.
2. Move the operating
switch to the "II"
(Ventilate) position.
Thermostatic regulation and
heating operation are not possible
in this operating mode.
Fuel filter
The fuel filter [
] must be checked
for dirt or paraffin formation
before the unit is started.
Paraffin formation with low
outside temperatures.
Even at low temperatures, an
adequate supply of flowing
heating oil must be ensured.
■
The in-built fuel pre-heating
[
] is activated only when
the power plug is connected
to a functional mains socket
and the ambient temperature is
lower than 10°C
■
It is not possible to rectify
paraffin separation that
has already occurred with
the heating. If paraffin has
already formed it is necessary
to clean out the complete fuel
system