Tab.6
Central heating circuit data
Quinta Pro
30
45
55
65
90
115
Water content
l
4.3
4.3
6.4
6.4
9.4
9.4
Water operating pressure
min
bar
0.8
0.8
0.8
0.8
0.8
0.8
Water operating pressure (PMS) max
bar
4.0
4.0
4.0
4.0
4.0
4.0
Water temperature
max
°C
110.0
110.0
110.0
110.0
110.0
110.0
Operating temperature
max
°C
90.0
90.0
90.0
90.0
90.0
90.0
Hydraulic resistance (ΔT=20K)
mbar
70
90
130
140
140
250
Tab.7
Electrical data
Quinta Pro
30
45
55
65
90
115
Supply voltage
V~
230
230
230
230
230
230
Power consumption – full load
max
W
39
68
80
88
125
199
Power consumption - part load
max
W
18
18
23
23
20
45
Power consumption - standby
max
W
5
5
6
6
4
7
IP
X4D
X4D
X4D
X4D
Fuses
Main
PCU
A
6.3
2.0
6.3
2.0
6.3
2.0
6.3
2.0
6.3
2.0
6.3
2.0
(1) Splashproof; under certain conditions, the boiler may be installed in damp areas, such as bathrooms.
Tab.8
Other data
Quinta Pro
30
45
55
65
90
115
Total weight (empty)
kg
53
53
60
60
67
68
kg
49
49
56
56
65
65
Average acoustic level at a dis
tance of one metre from the boil
er
dB(A)
38
45
45
45
52
51
(1) Without front panel.
Tab.9
Technical parameters
Quinta Pro
30
45
55
65
90
115
Condensing boiler
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
B1 boiler
No
No
No
No
No
No
Cogeneration space heater
No
No
No
No
No
No
Combination heater
No
No
No
No
No
No
Rated heat output
Prated
kW
30
41
55
62
84
107
Useful heat output at nominal
heat output and high tempera
P
4
kW
29.8
40.8
55.3
61.5
84.2
107.0
Useful heat output at 30% of
rated heat output and low tem
P
1
kW
9.9
13.7
18.4
20.5
27.9
35.7
Seasonal space heating energy
efficiency
ƞ
s
%
94
94
93
94
-
-
3 Technical specifications
14
123157 - v.12 - 07022018