8 Operation
8.1
Use of the control panel
1 Display
2
Escape or
key
3
CH temperature or key
4
DHW temperature or key
5
Enter or
Cancel key lockout
6
Chimney-sweeping keys
Press the 2 and 3 keys simultaneously.
7
Menu keys
Press the 4 and 5 keys simultaneously.
8
On/off switch
The display has several positions and symbols and provides information
about the operating status of the boiler and any faults. A maintenance
message may also appear on the display. Numbers, dots and/or letters
may be shown. The symbols above the function keys indicate the current
function.
The display content can be changed using parameter
.
The brightness of the display lighting can be changed using parameter
.
Key lockout is activated by setting parameter
to . If no key is press
ed for 3 minutes, the display lighting switches off and only the current wa
ter pressure, the
key and the
symbol are displayed. Press the
key for approximately 2 seconds to reactivate the display and the oth
er keys. The
symbol disappears from the display.
8.2
Shutdown
If the central heating is not due to be used for a long period of time, it is
recommended that the boiler be disconnected from the power supply.
1. Shut off the gas supply.
2. Keep the area frost-free.
8.3
Frost protection
Caution
Drain the boiler and central heating system if you are not going
to use your home or the building for a long time and there is a
chance of frost.
The frost protection does not work if the boiler is out of opera
tion.
The built-in boiler protection is only activated for the boiler and
not for the system and radiators.
Open the valves of all the radiators connected to the system.
Set the temperature control low, for example to 10°C.
If there is no heat demand, the boiler will only switch on to protect itself
against frost.
If the temperature of the central heating water in the boiler drops too low,
the built-in boiler protection system is activated. This system works as fol
lows:
At a water temperature lower than 7°C, the heating pump starts.
If the water temperature is lower than 4°C, the boiler switches on.
If the water temperature is higher than 10℃ the boiler switches off and
the circulation pump continues to run for a short time.
Fig.44
Control panel
AD-0000065-01
1
2
3
4
5
8
6
7
8 Operation
123157 - v.12 - 07022018
49