6.6.15 Start and end point analog signal (
Q
and
Y
)
Start point (0 Volt): adjustable between
5)
(-50)°C and +
50
°C, factory default
00
°C.
This value sets the required flow temp at 0 Volt signal input (restricted by the min flow
set point).
End point (10 Volt): adjustable b
51
°C and
((
(+299)°C, factory default
)0
(100)°C.
This value sets the required flow temp at 10 Volt signal input (restricted by the max
flow set point).
NOTE:
These settings are only applicable when boiler control operation parameter
(
A
) has the
x
value set to
4
.
6.7 Read-out mode (
X00
)
To check boiler set points and values.
Using the ‘
m
’-key, press repeatedly until
!
(flashing dot) appears in the ‘
code’
-display.
Then select the required code
@
,
#
or
$
etc. using the ‘
s
’-key.
Code
Description
Read-out
(example)
!
Actual flow temperature
80
@
Actual return temperature
70
#
Actual DHW temperature (only with sensor)
58
$
Actual outdoor temperature (with Chronotherm sensor)
05
%
n/a
3&
^
Flow temperature (set point)
80
&
Actual heat demand status
1x
= demand;
0x
= no demand
*
Calculated HTG cut-in temperature
67
(
Actual flow temperature rise [0.1 °C/sec]
02
A
n/a
Table 10 Read-out mode user level