8 ELECTRICAL
INSTALLATION
8.1 General
The Remeha Quinta 85 is supplied as standard with electronic control and flame
ionisation safety controls with a specially designed microprocessor at the heart of the
control system.
8.2 Specifications
8.2.1 Electrical
supply
The Remeha Quinta 85 must have a permanent 230V-50Hz single phase supply rated
at 6.3 Amps. The control unit is not phase / neutral sensitive.
8.2.2 Control
box
Manufacture:
Gasmodul
Model:
MCBA
1461
D
Supply voltage:
230 V/50 Hz
Electrical rating:
10 VA
Pre-purge time:
4.2 seconds
Post-purge time:
10 seconds
Safety time:
4.2 seconds maximum
Anti-hunting time:
150 seconds
Pump run on (HTG):
1 - 15 minutes
Pump run on (DHW):
5 minutes
8.2.3 Fuse
specification
The boiler is protected by fuses:
- on the main power supply located
in the euro connector socket rated
at 6.3 amps (slow acting). Spare
fuse is supplied - located in the euro
connector socket
- control circuit 230 Volt - located on the
Gasmodul control box, ref. F1 rated at
2 amps (fast acting)
- control circuit 24 Volt dc- located on
the Gasmodul control box, ref. F2
rated at 3.15 amps (slow acting)
Spare fuses are supplied - located on the
Gasmodul control box cover.
Fig. 12
Gasmodul control box
00.W4H.79.00018
NOTE:
Do not use connector X8!