Remeha Gas HP 35 A
(LT/HT)
26
must be secured (separated acoustically) to the lower frame to
SURYLGHVXI¿FLHQWUHVLVWDQFHWRWKHZHDWKHU
m
CAUTION
Do not use wooden shims as these are quickly affected by
moisture.
Free space
3RVLWLRQWKHKHDWSXPSV\VWHPVRWKDWWKHUHLVVXI¿FLHQW
distance from combustible surfaces, walls or other appliances.
Maintain the minimum distance as indicated in
Fig. 16.
A minimum amount of free space is needed in order to perform
PDLQWHQDQFHRQWKHV\VWHPDQGWRJXDUDQWHHVXI¿FLHQWDLU
supply for the fans in the heat pumps. Create a gangway
around the system, if necessary.
7.3.3 Hydraulic
connections
General guidelines
Use pipes made from stainless steel, steel, copper or
cross-linked polyethylene that is suitable for this purpose.
$OOZDWHUSLSHVDQGFRQQHFWLRQVPXVWEHVXI¿FLHQWO\
insulated, in accordance with current standards, in order to
prevent loss of heat and the development of condensation.
m
WARNING
Do not use galvanised pipes or connections when using a
glycol mixture as the antifreeze agent. This is because of the
risk of corrosion.
Use anti-vibration connecting pieces to prevent vibrations
when rigid pipes are used for the system's water supply
and discharge.
T004103-A
450
450
800
600
Fig. 16
Minimum amount of free space around the heat pump system