Remcor SID350A/35S Operator'S Manual Download Page 32

29

91626

2.D FROZEN EVAPORATOR

1. SHUTOFF ICEMAKER AND THAW EVAPORATOR.
2. START ICEMAKER

IS

AMBIENT ABOVE

60

°

F?

IS

VOLTAGE WITHIN

¦

10%

WAIT AND TIME ONE FULL

FREEZING CYCLE, 10-11 MIN.

ARE ALL

TIMING FUNCTIONS

ACCURATE TO SETTINGS

¦

10%

DOES

HOT GAS VALVE

ENERGIZE

YES

YES

YES

DOES

HARVEST MOTOR

OPERATE

DOES

ICE HARVEST

NORMALLY

YES

YES

YES

1. ARRANGE TO MAINTAIN MINIMUM 60

°

F

AMBIENT.

2. CONTACT REMCOR REGARDING SPECIAL

APPLICATION.

CHECK VOLTAGE ITEMS IN 1.

1. CHECK WIRING.
2. CHECK TIMERS.

CHECK HOT GAS VALVE AND

COMPONENT OPERATION.

CHECK HARVEST MOTOR

AND CAPACITOR.

NO

NO

NO

NO

NO

1. REPEAT HARVEST COMPONENT TEST.
2. ADJUST ICE THICKNESS WITH TIME

ADJUSTMENTS, AFTER ALL OTHER

FACTORS HAVE BEEN CHECKED

THOROUGHLY.

NO

Summary of Contents for SID350A/35S

Page 1: ...D IN U S A REMCOR INC 8 95 Part No 91626 Revised June 1997 Revision B THIS DOCUMENT CONTAINS IMPORTANT INFORMATION This Manual must be read and understood before installing or operating this equipment...

Page 2: ...R FREEZE UP 16 SERVICE PROCEDURES 17 HIGH PRESSURE CONTROL 17 BIN THERMOSTAT 17 CONDENSER AIR COOLED 18 TROUBLESHOOTING GUIDE 23 WARRANTY 37 LIST OF FIGURES FIGURE 1 SID 350 35S 4 FIGURE 2 SID 350 35S...

Page 3: ...AKER CAPACITIES LBS DAY 2 TABLE 3 CONTROLLER 9 Manufactured Under One or More of the Following Patent Numbers 3 211 336 3 274 792 3 393 839 3 517 860 3 739 842 4 215 803 4 227 377 4 300 3594 346 824 C...

Page 4: ...t panels are securely fastened ALWAYS keep area around the dispenser clean of ice cubes IMPORTANT INSTALLATION NOTICE An Everpure Model 9320 42 System IV Model DB900 or equal icemaker quality water tr...

Page 5: ...tion Table 1 Specifications Compressor HP 1 2 Refrigerant R 22 1 lb Pressure Controls Setting High 400 Psig Low 10 Psig Voltage 115 1 60 Amps 16 Amps Circuit Ampacity 20 Amps Fuse Size 20 Amps Ice Sto...

Page 6: ...code of the Building Officials and Code Administrators International Inc BOCA and the Food Service Sanitation Manual of the Food and Drug Administration Do not install unit on a water softener line It...

Page 7: ...air flow out 2 Inlet air flow may only be restricted on one side at least one side must be open for proper performance 3 Minimum top clearance must be 11 500 AIR FLO W AIR FLO W 18 188 10 625 3 500 13...

Page 8: ...flow out 2 Inlet air flow may only be restricted on one side at least one side must be open for proper performance 3 Minimum top clearance must be 11 500 AIR FLO W AIR FLO W 18 188 10 625 3 500 13 500...

Page 9: ...OPENING NOTE DRAIN COLLECTOR REQUIRES 1 IN BARB BY MPT 1 IN I D PLASTIC TUBING WATER COOLED CONDENSER INLET 3 8 O D COMP FITTING 1 1 4 IN DIA CLEARANCE HOLE BEVERAGE TUBING CUTOUT FOR B MODELS ONLY IC...

Page 10: ...nit 3 Put the stop rum switch in the run position Observe that the icemaker goes through proper icemaking and harvest cycle If unit malfunctions consult troubleshooting section NOTE Do to meltage loss...

Page 11: ...OPTIONAL FOR DIET OR ROOT BEER 5 15 PSIG 15 50 PSIG REGULATORS CO 2 TANK SYRUP TANKS S1 S2 S3 S4 1 2 3 4 CW CW 60 100 PSIG DOUBLE CHECK VALVE FILTER CARBONATOR OPTIONAL PRESSURE REGULATOR WATER SUPPL...

Page 12: ...motor and agitator motors off 2 Water fill valve off 35 570 seconds air cooled 35 510 seconds water cooled X 1 Hot gas solenoid valve closed At the 35 second point in the cycle the host gas solenoid...

Page 13: ...YCLE TIMER RCT 2 1 CONDENSER FAN AIR COOLED STOP RUN RED BLUE BLUE RED C NO NC C NO NC C NO NC CLEAN RUN F CAP VEND SWITCH GATE SOLENOID AGITATOR MOTOR WATER FILL VALVE HG SOL VALVE AIR PUMP HARVEST M...

Page 14: ...COMPRESSOR MOTOR START RELAY YEL BLK RED BLUE RED S R C COMPRESSOR START CAP C 2 1 3 S R COMPRESSOR ELECTRIC BOX RED RED RED RED YEL BLUE BLUE COND FAN MOTOR AIR COOLED GATE SOLENOID HARVEST MOTOR RE...

Page 15: ...DRAIN CITY WATER PRESSURE REGULATING VALVE WATER COOLED MODELS FILTER DRIER B A CONDENSER FAN LOW PRESSURE SERVICE PORT CONDENSER AIR COOLED MODELS COMPRESSOR HOT GAS SOLENOID VALVE HIGH PRESSURE CON...

Page 16: ...front panel and right side access panel 2 Put toe stop run switch in the stop position at the end of the harvest cycle An alternate method would be to stop the unit during the icemaking cycle and allo...

Page 17: ...per and wash and rinse it thoroughly 3 Wash down all inside surfaces of the ice storage area including the top cover with a mild detergent solution and rinse thoroughly to remove all traces of deterge...

Page 18: ...syrup C Disconnect the cleaning tank and hook up the sanitizing tank to the syrup line and CO2 system D Energize the beverage faucet until the chlorine sanitizing solution is dispensed through the fau...

Page 19: ...harvested should be 1 9 to 2 1 pounds A Put the stop run switch in the stop position if the unit is in the icemaking cycle stop the unit at the end of the harvest cycle 3 If ice weight is not in the...

Page 20: ...is located on the top of the control Bin Thermostat 1 The bin thermostat is located in the upper right rear corner of the unit under the cabinet flange 2 To adjust the thermostat remove the top plasti...

Page 21: ...the discharge and suction of the air pump 7 Remove the pins from behind the front cabinet flanges at the sink 8 Remove sink 9 Remove bracket mounting evaporator assembly to the cabinet 10 Loosen two 2...

Page 22: ...ressor electric box Remove the four 4 mounting screws securing the fan motor bracket to the con densing unit assembly base Remove the complete motor bracket fan blade assembly from the unit for ease o...

Page 23: ...e installation of the fill valve Compressor The compressor can exhibit basically two types of malfunctions It will run but the refrigeration system produces little or no ice In this case check the suc...

Page 24: ...s sure 300 PSIG and suction pressure 17 35 PSIG at 70 F ambient air temperature and 50 F water temperature B Check ice production capacity see ice thickness adjustment section for procedure Hot Gas Va...

Page 25: ...er 4 After completion of the hot gas cycle check for voltage at the NC terminals if the RCT and neutral If there is no voltage at either or both of these terminals the timer is defective 5 If voltage...

Page 26: ...iate answer to each question 2 Dot not skip any section unless instructed to do so You might miss the solution to your problem 3 Evaluate the possible problem causes in the sequence in which they are...

Page 27: ...TO 1 IS ICEMAKER O K ICEMAKER ABNORMAL DISPENSER AND BEVERAGE WORK NORMALLY GO TO 2 GO TO 1 IS DISPENSER O K DOES NOT DISPENSE ICEMAKER WORKS O K GO TO 3 YES YES NO NO NO YES NO PROBLEM WITH BEVERAGE...

Page 28: ...CIRCUIT IN WIRING INSIDE UNIT 2 CHECK COMPONENTS FOR SHORT CIRCUIT OR GROUNDED WIRING YES REPLACE WITH CORRECT SIZE DEVICE NO IS LINE VOLTAGE HIGH OR LOW NO YES LOW HIGH IS OTHER EQUIP ON SAME CIRCUIT...

Page 29: ...AIR RECIRCULATING TO AIR CONDENSER ELIMINATE BY BAFFLING 3 CHECK FOR DIRTY AIR COOLED CONDENSER 4 CHECK CONDENSER FAN MOTOR 5 CHECK FOR REFRIGERANT OVER CHARGE WATER COOLED UNITS 1 CHECK EATER SUPPLY...

Page 30: ...VOLTAGE CHECK VOLTAGE PROBLEMS IN 1 NO IS THERMAL PROTECTOR OPEN IS COMPRESSOR BODY COLD 1 CHECK FOR LOOSE OR BROKEN WIRING CONNECTION IN COMPRESSOR POWER CIRCUIT 2 CHECK STARTING RELAY 3 CHECK CAPACI...

Page 31: ...OLD IS HOT GAS SOLENOID ENERGIZED 1 CHECK FOR REFRIGERANT UNDER CHARGE 2 CHECK HOT GAS SOLENOID FOR LEAKING SEAT 3 GO TO 2 A CHECK HOT GAS VALVE CIRCUIT IS WATER LEVEL NORMAL CHECK WATER PROBLEM IN 2...

Page 32: ...IZE YES YES YES DOES HARVEST MOTOR OPERATE DOES ICE HARVEST NORMALLY YES YES YES 1 ARRANGE TO MAINTAIN MINIMUM 60 F AMBIENT 2 CONTACT REMCOR REGARDING SPECIAL APPLICATION CHECK VOLTAGE ITEMS IN 1 1 CH...

Page 33: ...S WATER TEMP HIGH IS AMBIENT TEMP HIGH IS ICE THIN CHECK WATER ITEMS IN 2 A NORMAL EFFECT INSTALL PRE COOLER TO INCREASE CAPACITY NORMAL EFFECT ARRANGE FOR LOWER AMBIENT AIR TEMP IF POSSIBLE GO TO 2 C...

Page 34: ...QUALITY IS ICE CLOUDY IS ICE SOFT 1 CHECK AIR PUMP 2 CHECK ADJUSTMENT OF TIMER WATER DUMP 3 CHECK WATER FILTER 4 INCREASE WATER DUMP BY ADJUSTING TIMER 5 INSTALL ADDITIONAL WATER TREATMENT DEVICES FOR...

Page 35: ...TOO HIGH 1 CHECK FOR BLOWN SOLENOID FUSE IN ELECTRIC BOX IF FUSE IS BLOWN CHECK FOR STUCK GATE MECHANISM BURNED OUT SOLENOID OR LOW VOLTAGE 2 CHECK VEND SWITCH 3 CHECK FOR LOOSE OR BROKEN WIRE CONNECT...

Page 36: ...ONS FROM 24 V TRANSFORMER 4 CHECK 24 V TRANSFORMER 1 CHECK REMOTE COOLING SYSTEM B MODELS 2 CHECK FOR ICE ON COLD PLATE BC MODELS 1 CHECK CO2 PRESSURE 2 CHECK CARBONATOR 1 CHECK WATER SUPPLY PRESSURE...

Page 37: ...ow Pressure Control 12 60501 60501 High Pressure Control 13 51485 51485 Evaporator Shell Foamed 14 50481 50481 Gasket 15 51163 51163 Gasket Shaft Sea 16 51422 51422 Gasket Evaporator 17 32777 32777 Co...

Page 38: ...70 Merchandiser Assy 11 32838 Dispenser Switch Actuator 12 21517 Agitator 13 31093 Solenoid Assy 14 52005 Cover Top 15 31106 Agitator Motor 16 27880 Panel Access RS 17 31620 Starter Fluorescent Light...

Page 39: ...Assembly 7 70423 1 Cotter Pin 8 10080 1 Gate Lift Rod 9 10081 1 Gate Lift Rod Bushing 10 50754 1 Gate Arm Bearing 11 21492 1 Gate Lift Arm 12 70043 1 Flatwasher 13 70422 1 Spring 14 70263 1 1 4 20 x...

Page 40: ...29 ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE B49 6 EU ENGLAND D 44 789 763 101 D FAX 44 789 763 644 FRANCE D 71 ROUTE DE ST DENIS D F 95170 DEUIL LA BARRE D PARIS FRANCE D 33 1 34 28 6200 D FAX 3...

Page 41: ...CORPORATE HEADQUARTERS Remcor Incorporated 500 Regency Drive Glendale Heights IL 60139 708 980 6900...

Reviews: