Unit data KWE 1550-2100 Eco
Series
KWE
1550 Eco
KWE
1600 Eco
KWE
1850 Eco
KWE
2100 Eco
Operating mode
Air-cooled chiller for external installation in high-effi-
ciency design for cooling
Nominal cooling output
1)
kW
155.3
161.3
186.3
211.4
SEER
4.9
5.3
Annual room cooling efficiency
ŋ
S,C
%
183
187
203
205
Adjustment range - return temperature
cooling
°C
+5 to +18
Operating range, cooling
°C
+5 to +48 / -15 to +48
3)
Cooling circuits, number
2
Refrigerant
R452B
GWP value
676
Refrigerant filling quantity
kg
15.0
18.0
18.5
CO
2
equivalent
t
10.1
12.2
12.5
Compressor, number
4
Nominal flow rate
m
3
/h
39,000
58,500
Number of fans
2
3
Sound pressure level
2)
dB (A)
58.8
60.0
60.2
60.5
Sound power level
dB (A)
90.7
92.0
92.2
92.5
Power supply
V/Ph/Hz
400/3~N / 50
Enclosure class
IP
X4
Electrical current consumption, max.
A
160.7
163.9
188.7
213.5
Electrical rated power consumption,
cooling
kW
52.1
51.9
56.2
62.7
Electrical rated current consumption,
cooling
A
94.1
93.8
101.4
113.2
Operating medium
Water; max. 35% ethylene glycol, max. 35% propy-
lene glycol
Operating pressure, medium, max.
kPa
800
Nominal flow rate, cooling
m
3
/h
26.7
27.7
32.0
36.3
Minimum flow volume, medium
m
3
/h
16.0
16.6
19.2
21.8
Maximum flow volume, medium
m
3
/h
42.7
44.3
51.2
58.1
Pressure loss, indoor
kPa
37.5
39.9
50.8
47.3
15
Summary of Contents for KWE 1060 Eco
Page 61: ...V Valves for hydronic balancing 45 54 W Warranty 5 61...
Page 62: ...REMKO KWE Eco series 62...