Manuale d’uso -
19
Register
Name
Comment
Register Type R/W Default
Value
Range
Modbus
Address
STATUS 100
bit 0: flash settings error;
bit1: flash calibration error;
bit 2: Voltage Over Range;
bit 3: Voltage Under Range;
bit [4:5] Reserved;
bit 6: Zero crossing detecting;
bit[7:9] Reserved;
bit 10: Energy storing error;
bit11: Energy initialization error;
bit 12: Reserved;
bit 13: Current Over Range;
bit 14: Current Under Range;
Unsigned short
R
40192
V RMS 100
Voltage RMS measurement (V/100)
in hundredths
Signed long
(LSW first)
R
40193
40194
I RMS 100
Current RMS measurement (mA/100)
in hundredths
Signed long
(LSW first)
R
40195
40196
P 100
Power measurement (W/100) in
hundredths
Signed long
(LSW first)
R
40197
40198
Q 100
Reactive Power measurement
(VAR/100) in hundredths
Signed long
(LSW first)
R
40199
40200
S 100
Apparent Power measurement
(VA/100) in hundredths
Signed long
(LSW first)
R
40201
40202
Cosφ 100
Cosφ measurement in hundredths
Signed long
(LSW first)
R
40203
40204
Frequency 100 Frequency measurement (Hz/100) in
hundredths
Signed long
(LSW first)
R
40205
40206
THD 100
THD in hundredths
Signed long
(LSW first)
R
40207
40208
Energy 100 Total Energy measurement
(KWh/100) in hundredths
Signed long
(LSW first)
R
40209
40210
Energy positive
100
Only positive Energy Measurement
(KWh/100) in hundredths
Signed long
(LSW first)
R
40211
40212
Energy
negative 100
Only negative Energy Measurement
(KWh/100) in hundredths
Signed long
(LSW first)
R
40213
40214
V peak 100 Instantaneous Voltage Peak (V/100)
in hundredths
Signed long
(LSW first)
R/W
40215
40216
I peak 100
Instantaneous Current Peak
(mA/100) in hundredths
Signed long
(LSW first)
R/W
40217
40218
V MAX 100 Max RMS Voltage (V/100) in
hundredths
Signed long
(LSW first)
R/W
40219
40220
V min 100
Min RMS Voltage (V/100) in
hundredths
Signed long
(LSW first)
R/W
40221
40222