background image

Start Up Conditions

DRAFT HOOD OPERATION

Check draft hood operation by performing a worst case

depressurization of the building.  With all doors and windows

closed, and with all air handling equipment and exhaust fans

operating, such furnaces, clothes dryers, range hoods and

bathroom fans, a match flame should still be drawn into the

draft hood of the water heater with its burner firing.  If the

flame is not drawn toward the draft hood, shut off the water

heater and make necessary air supply changes to correct.

CONDENSATION

Whenever the water heater is filled with cold water, a certain

amount of condensation will form while the burner is on. A

water heater may appear to be leaking when in fact the water

is condensation. This usually happens when:

a. When a new water heater is filled with cold water for the

first time.

b. When gas burns and water vapor is produced in water

heaters, particularly high efficiency models where flue

temperatures are lower.

c. When you use large amounts of hot water in a short time

and the refill water is very cold.

Moisture from the products of combustion condense on the

cooler tank surfaces and form drops of water which may fall

onto the burner or other hot surfaces to produce a “sizzling”

or “frying” noise.

Excessive condensation can cause pilot outage due to water

running down the flue tube onto the main burner and putting

out the pilot.

Because of the suddenness and amount of water, condensa-

tion water may be diagnosed as a “tank leak”. After the water

in the tank warms up (about 1-2 hours), the condition should

disappear.

Do not assume the water heater is leaking until there has been

enough time for the water in the tank to warm up.

An undersized water heater will cause more condensation.

The water heater must be sized properly to meet the family’s

demands for hot water including dishwashers, washing

machines and shower heads.

Excessive condensation may be noticed during the winter and

early spring months when incoming water temperatures are at

their lowest.

Good venting is essential for a gas fired water heater to oper-

ate properly as well as to carry away products of combustion

and water vapor.

SMOKE/ODOR

It is not uncommon to experience a small amount of smoke

and odor during the initial start-up. This is due to burning off

of oil from metal parts, and will disappear in a short while.

THERMAL EXPANSION

Water supply systems may, because of such events as high line

pressure, frequent cut-offs, the effects of water hammer among

others, have installed devices such as pressure reducing

valves, check valves, back flow preventers, etc...to control

these types of problems. When these devices are not equipped

with an internal by-pass, and no other measures are taken, the

devices cause the water system to be closed. As water is heat-

ed, it expands (thermal expansion) and closed systems do not

allow for the expansion of heated water.

The water within the water heater tank expands as it is heated

and increases the pressure of the water system. If the relieving

point of the water heater’s temperature-pressure relief valve is

reached, the valve will relieve the excess pressure. 

The tem-

perature-pressure relief valve is not intended for the constant

relief of thermal expansion.

This is an unacceptable condition

and must be corrected.

It is recommended that any devices installed which could cre-

ate a closed system have a by-pass and/or the system have an

expansion tank to relieve the pressure built by thermal expan-

sion in the water system. Expansion tanks are available for

ordering through a local plumbing contractor. Contact the

local water supplier and/or plumbing inspector for assistance

in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some

metal parts during periods of heat-up and cool-down do not

represent harmful or dangerous conditions.

Condensation causes sizzling and popping with the burner

area during heating and cooling periods and should be con-

sidered normal. See “Condensation” in this section.

Operational Conditions

SMELLY WATER

In each water heater there is installed at least on anode rod

(see parts section) for corrosion protection of the tank. Certain

water conditions will cause a reaction between this rod and

the water. The most common complaint associated with the

anode rod is one of a “rotten egg smell”. This odor is derived

from hydrogen sulfide gas dissolved in the water. The smell is

the result of four factors which must all be present for the odor

to develop:

a. a concentration of sulfate in the supply water.

b. little or no dissolved oxygen in the water.

c. a sulfate reducing bacteria within the water heater. (This

harmless bacteria is non-toxic to humans.)

d. an excess of active hydrogen in the tank. This is caused

by the corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water

heater models by replacing the anode(s) with one of less active

material, and then chlorinating the water heater tank and all

hot water lines. Contact the local water heater supplier for fur-

ther information concerning an Anode Replacement Kit

#9000029 and this Chlorination Treatment.

For Your Information

19

Summary of Contents for 184123-000

Page 1: ... phone Follow the gas suppli er s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death Improper installation adjustment ...

Page 2: ...ated gas in the area Search for odor of gas by sniffing at ground level in the vicinity of the appli ance If odor is detected follow steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING Improper installation adjustment alteration service or maintenance can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE Refer to this manual for assis tance or cal...

Page 3: ...oors Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation WARNING Obstructed or deteriorated vent systems may present a serious health risk or asphyxiation WARNING Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chemical vapors Spray can pro...

Page 4: ... Propane L P Gas To Natural Gas 14 Installation Checklist 15 Lighting 16 17 Temperature Regulation 18 For Your Information 19 20 Start Up Conditions 19 Draft Hood Operation 19 Condensation 19 Smoke Odor 19 Thermal Expansion 19 Strange Sounds 19 Operational Conditions 19 20 Smelly Water 19 20 Air In Hot Water Faucets 20 High Temperature Shut Off System 20 Not Enough or No Hot Water 20 Water Is Too ...

Page 5: ...se DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fired water heater It also contains warnings through out the manu al that you must read and be aware of All warnings and all instructions are essential to the proper opera tion of the water heater and your safety Since we can not put everything on the fi...

Page 6: ...m requires water at temperatures higher than required for other uses the hot water system may require a means such as a mixing valve to be installed to temper the water at certain points of use Some peo ple are more likely to be permanently injured by hot water than others these include the elderly children the infirm or the physically mentally handicapped Before immersing yourself or anyone else ...

Page 7: ...consult these manufacturers for correct sizing If the opening is covered by louvers or screen the total free area must be 32 square inches Locating the New Water Heater When a drain pan is required an exterior door with lou vered openings must be used as shown in figure 1 page 6 INSTALLATION CLEARANCES TOP VIEW 1 MIN 1 MIN 4 MIN 1 MIN NOTE DOOR MUST BE ON OUTSIDE WALL OF MANUFACTURED HOME Figure 3...

Page 8: ...on or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this warning may result in a fire hazard WARNING Minimum clearances between the water heater and combustible and noncombustible construction are 1 at the sides and rear 4 at the front and 6 from the vent pipe Clearance from the top of the draft hood is 12 Refer to the label on t...

Page 9: ...ystem shall be subjected to a pres sure test The test shall be made by subjecting the sys tem to air or water at 100 psi for 15 minutes without loss of pressure When air pressure is used the water heater shall not be connected during the test WHEN AIR TESTING REMOVE THE WATER LINES FROM THE WATER HEATER HOT OUTLET COLD INLET 9 WARNING This water heater shall not be connected to any heating systems...

Page 10: ...g must not be blocked or reduced in size under any circumstances Excessive length over 30 feet or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between the relief valve and the tank Do not connect tubing directly to discharge drain unless a 6 air gap is provided To prevent bodily injury hazard to life...

Page 11: ...od legs in the receiving holes on the top of the water heater The legs will snap in the holes to give a tight fit 2 Place the vent pipe over the draft hood With the vent pipe in position drill a small hole through both the vent pipe and draft hood Secure them together with a sheet metal screw CAUTION Never use this water heater unless it is completely filled with water To prevent damage to the tan...

Page 12: ... chemical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemicals calcium and sodium chloride waxes bleach and process chemicals are typical compounds which are potentially corrosive WARNING Make sure the gas supplied is the same type listed on the model rating plate The inlet gas pressure must not exceed 10 5 in water column 2 6kPa for ...

Page 13: ...d from PILOT to OFF unless knob is depressed slightly DO NOT FORCE Step 11 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety in formation on For Your Safety label If you don t smell gas go to the next step Step 12 Find pilot follow metal tube from gas control The pilot is located in front of the burner See Figure 7 page 14 Step 13 If you don t smell gas tur...

Page 14: ...ilot orifice G brass color and in Step 8 turn control screw B in Figure 4 clockwise to stop Screw must be in OUT posi tion for Natural gas See Instruction Label for orifice sizes Maximum Supply Pressure 10 5 W C For Nat Gas 13 W C for Propane L P Gas Minimum Supply Pressure 5 W C for Nat Gas 11 W C For Propane L P Gas Installing the New Water Heater cont d B A GAS CONTROL KNOB TEMPERATURE ADJ DIAL...

Page 15: ...URE RELIEF VALVE TEE SHUTOFF VALVE DISCHARGE PIPE Do not cap or plug Must terminate beneath manufactured home MODEL RATING PLATE 6 Is there proper clearance between the water heater and anything that might catch fire See the Locating the New Water Heater section 7 Do you have adequate ventilation so that the water heater will operate properly See the Locating the New Water Heater section 8 Is the ...

Page 16: ...e attempting to light or relight the water heater s pilot or turning on a nearby electrical light switch be absolutely sure there is no accumulated gas in the area Search for odor of gas by sniffing at ground level in the vicinity of the appliance If odor is detected follow the steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING AN ODORANT IS ADDED T...

Page 17: ...his label If you don t smell gas go to the next step 6 Remove or open inner door located below the gas control unit Figure 11 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner 8 If you don t smell gas turn knob on gas control counter clockwise to PILOT position Figure 9 9 Push in control knob all the way and hold down Immediately light the pilot with a mat...

Page 18: ...RNING HOTTER WATER CAN SCALD Water heaters are intended to produce hot water Water heated to a temperature which will satisfy clothes washing dish washing and other sanitizing needs can scald and permanently injure you upon contact Some people are more likely to be permanently injured by hot water than others These include the elderly children the infirm or physically mentally handicapped If anyon...

Page 19: ... others have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heat ed it expands thermal expansion and closed systems do not allow for the expansion of heated water The wat...

Page 20: ...eat the water and seem like less hot water 9 If you cannot find what is wrong call the local gas utility and or plumbing contractor WATER IS TOO HOT 1 The temperature adjustment dial may be set too high See the Temperature Adjustment section NOTE A period of time is necessary after an adjust ment has been made for the water temperature to reach the new temperature setting 2 If lower temperature se...

Page 21: ...G Obstructions and deteriorated vent systems may pre sent serious health risk or asphyxiation WARNING Chemical vapor corrosion of the flue and vent system may occur if air for combustion contains certain chem ical vapors Spray can propellants cleaning solvents refrigerator and air conditioner refrigerants swimming pool chemicals calcium and sodium chloride waxes bleach and process chemicals are ty...

Page 22: ...r heater Failure to install and maintain a new properly listed tempera ture pressure relief valve will release the manufacturer from any claim which might result from excessive temperature or pressure TEMPERATURE PRESSURE RELIEF VALVE DISCHARGE PIPE 22 WARNING When checking the temperature pressure relief valve oper ation make sure that 1 no one is in front of or around the outlet of the temperatu...

Page 23: ...form and drip into the fire or run on the floor This is common at the time of startup after installation and when incoming water is cold Water in the water heater bottom or on the floor may be from condensation loose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other a...

Page 24: ...Illustrated Now that you have purchased this Water Heater should a need ever exist for repair parts or service simply contact the com pany it was purchased from or direct from the manufacturer listed on the model rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on request or parts will be shipped at prevailing price and...

Reviews: