background image

Multilingual document:  

Select your language below

Model RFC43

Model RFC30

Model RFC49

Model RFC58

Solid

Perforated

Model RFC Cover Plate

www.reliablesprinkler.com

Table A

Sprinkler Model

Nominal K-Factor

gpm/psi

½ 

(l/min/bar

½

)

Max. Coverage Area

ft x ft (m x m)

Sprinkler Identification  

Number (SIN)

RFC30

3.0 (43.2)

14 x 14  (4.3 x 4.3)

RA0611

RFC43

4.3 (62)

20 x 20  (6.1 x 6.1)

RA0612

RFC49

4.9 (70.6)

20 x 20  (6.1 x 6.1)

RA0616

RFC58

5.8 (84)

20 x 20  (6.1 x 6.1)

RA0613

Product Description

Model RFC Series residential sprinklers are flat cover plate, 
concealed pendent sprinklers intended for installation in accor-
dance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers 
are cULus Listed as Residential Sprinklers in accordance with 
UL 1626.

Model RFC30, RFC43, and RFC49 sprinklers have a 165 °F 
(74 °C) temperature rated fusible-link operating element. Mod-
el RFC58 sprinklers are offered with either a 165 °F (74 °C) or 
212 °F (100 °C) temperature rated fusible-link operating ele-
ment. Sprinklers with a 165 °F (74 °C) temperature rating are 
ordinary temperature classification and should be used with a 
135 °F (57 °C) temperature rated cover plate. Sprinklers with a 
212 °F (100 °C) temperature rating are intermediate tempera-
ture classification and should be used with a 165 °F (74 °C) 
temperature rated cover plate.

Model RFC Series sprinklers are installed with a Model RFC 
cover plate. Model RFC cover plates may be installed by ei-
ther pushing or threading the cover plate into the sprinkler 
cup. Model RFC30, RFC43, and RFC49 sprinklers allow 1/2" 
(13 mm) of cover plate adjustment. Model RFC58 sprinklers 
allow 3/4" (19 mm) of cover plate adjustment. 

Model RFC cover plates are available in a variety of finishes as 
listed in Table H. In addition, Model RFC cover plates may be 
ordered as either traditional solid cover plates or perforated 
cover plates.

Product Features

•  

cULus Listed as Residential Sprinklers

•  

Push-On cover plate installation

•  

Low water flow requirements

Bulletin 006 Rev. K February 2017

cULus Listed

Model RFC Series Residential Sprinklers

Flat Cover Plate, Concealed Pendent Sprinkler

Summary of Contents for RFC Series

Page 1: ...operating ele ment Sprinklers with a 165 F 74 C temperature rating are ordinary temperature classification and should be used with a 135 F 57 C temperature rated cover plate Sprinklers with a 212 F 10...

Page 2: ...essure Max Coverage Area ft x ft m x m Flow gpm l min Pressure psi bar 12x12 3 6x3 6 9 34 9 0 0 62 14x14 4 3x4 3 10 38 11 0 0 76 Table B Model RFC30 Sprinkler Hydraulic Design Criteria Figure 1 Model...

Page 3: ...12x12 3 6x3 6 12 45 7 8 0 54 14x14 4 3x4 3 13 49 9 1 0 63 16x16 4 9x4 9 13 49 9 1 0 63 18x18 5 5x5 5 18 68 17 5 1 21 20x20 6 1x6 1 21 79 23 8 1 64 Table C Model RFC43 Sprinkler Hydraulic Design Crite...

Page 4: ...m l min Pressure psi bar 16x16 4 9x4 9 13 49 0 7 0 0 48 18x18 5 5x5 5 17 64 3 12 0 0 83 20x20 6 1x6 1 20 75 7 16 7 1 15 Table D Model RFC49 Sprinkler Hydraulic Design Criteria Figure 3 Model RFC49 Spr...

Page 5: ...16 60 6 7 6 0 53 18x18 5 5x5 5 18 68 1 9 6 0 66 20x20 6 1x6 1 20 75 7 11 9 0 82 Table E Model RFC58 Sprinkler Hydraulic Design Criteria Figure 4 Model RFC58 Sprinkler Components and Dimensions Sensit...

Page 6: ...t the Model FC wrench over the sprinkler until the wrench engages the body Do not wrench any other part of the sprinkler cup assembly The Model FC wrench is designed to be turned with a standard 1 2 s...

Page 7: ...ock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Prior to installation sprinklers should be maintained in the original cartons and packaging un...