Listings and Approvals

Listed by Underwriters Laboratories, Inc. and UL Certified for  
Canada (cULus)

UL Listing Category

Residential Automatic Sprinkler

UL Guide Number

VKKW

Model FC

Page 7 of 7

www.reliablesprinkler.com

Bulletin 006 Rev. K
February 2017

Maintenance

Model RFC series sprinklers should be inspected and the sprin-
kler system maintained in accordance with NFPA 25. Do not clean 
sprinklers with soap and water, ammonia or any other cleaning 
fluids. Remove dust by gentle vacuuming. Replace any sprinkler 
cover plate assembly which has been painted (other than facto-
ry applied) or damaged in any way. A stock of spare sprinklers 
should be maintained to allow quick replacement of damaged 
or operated sprinklers. Prior to installation, sprinklers should be 
maintained in the original cartons and packaging until used to 
minimize the potential for damage to sprinklers that would cause 
improper operation or non-operation.

Guarantee

For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms, 
and conditions, visit 

www.reliablesprinkler.com

.

Patents

Model RFC30, RFC43, RFC49, and RFC58 sprinklers are 
covered by U.S. Patent No. 9,248,327 and U.S. Patent No. 
7,275,603.

Model RFC30 and RFC43 sprinklers are additionally covered by 
U.S. Patent No. 8,776,903.

Ordering Information

Specify the following when ordering.

Sprinkler

 

•  Model (RFC30, RFC43, RFC49, RFC58)

 

•  Temperature Rating

Cover Plate

 

•  Model RFC

 

•  Temperature Rating

 

•  Finish (See Table H)

Sprinkler Wrench

 

•  Model FC

Summary of Contents for RFC Series

Page 1: ...operating ele ment Sprinklers with a 165 F 74 C temperature rating are ordinary temperature classification and should be used with a 135 F 57 C temperature rated cover plate Sprinklers with a 212 F 10...

Page 2: ...essure Max Coverage Area ft x ft m x m Flow gpm l min Pressure psi bar 12x12 3 6x3 6 9 34 9 0 0 62 14x14 4 3x4 3 10 38 11 0 0 76 Table B Model RFC30 Sprinkler Hydraulic Design Criteria Figure 1 Model...

Page 3: ...12x12 3 6x3 6 12 45 7 8 0 54 14x14 4 3x4 3 13 49 9 1 0 63 16x16 4 9x4 9 13 49 9 1 0 63 18x18 5 5x5 5 18 68 17 5 1 21 20x20 6 1x6 1 21 79 23 8 1 64 Table C Model RFC43 Sprinkler Hydraulic Design Crite...

Page 4: ...m l min Pressure psi bar 16x16 4 9x4 9 13 49 0 7 0 0 48 18x18 5 5x5 5 17 64 3 12 0 0 83 20x20 6 1x6 1 20 75 7 16 7 1 15 Table D Model RFC49 Sprinkler Hydraulic Design Criteria Figure 3 Model RFC49 Spr...

Page 5: ...16 60 6 7 6 0 53 18x18 5 5x5 5 18 68 1 9 6 0 66 20x20 6 1x6 1 20 75 7 11 9 0 82 Table E Model RFC58 Sprinkler Hydraulic Design Criteria Figure 4 Model RFC58 Sprinkler Components and Dimensions Sensit...