background image

Threads 

Body 

Fusible Link --....�-; 

Deflector (retracted) 

,-,'-!

11 

d) 

:  : 

1 1 

Pin (extende  � 

H

11  ,..

........ 

1 1 

Deflector (extended)  ��

Model RFC cover Plate 

3_5116" (84 mm) Dia. 

Reliabl� 

Ceiling

3

/

16

" (5 mm)

3‑

5

/

16

" (84 mm) Dia.

2‑

5

/

16

" (58 mm) 

Dia.

Model RFC cover plate

Deflector (extended)

Pin (extended)

Deflector (retracted)

Fusible link

Tower

1‑

3

/

4

" (44 mm) +/− 

1

/

4

" (6 mm)

Nominal face of fitting to ceiling

Cup

Body

Threads

Bottom View

Notes:

 

1.   For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a 

minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 

2.   For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.

Minimum Flow and Residual Pressure

Max. Coverage Area

ft. x ft.

(m x m)

Flow

gpm

(l/min)

Pressure

psi

(bar)

12 x 12

(3.6 x 3.6)

12

(45)

7.8

(0.54)

14 x 14

(4.3 x 4.3)

13

(49)

9.1

(0.63)

16 x 16

(4.9 x 4.9)

13

(49)

9.1

(0.63)

18 x 18

(5.5 x 5.5)

18

(68)

17.5

(1.21)

20 x 20

(6.1 x 6.1)

21

(79)

23.8

(1.64)

Table C

Model RFC43 Sprinkler Hydraulic Design Criteria

Figure 2

Model RFC43 Sprinkler Components and Dimensions

Cover Plate Finishes

(See Table H)

Sensitivity 

Fast‑response

Temperature Rating

165 °F (74 °C) sprinkler
135 °F (57 °C) cover plate

Cover Plate

Model RFC cover plate

Sprinkler Wrench

Model FC

Listings and Approvals

cULus Listed

Technical Specifications

Style:

 

Flat Concealed

 

Pendent

Threads:

 

1/2" NPT or ISO 7‑1 R 1/2

Nominal K-Factor:

 

4.3 (62 metric)

Max. Working Pressure:

 

175 psi (12 bar)

Min. Spacing:

 

8 ft (2.4 m)

Material Specifications

Thermal Sensor:

 

Nickel Alloy Solder Link

Sprinkler Body:

 

Brass Alloy

Levers:

 

Bronze Alloy

Yoke:

 

Brass Alloy

Sealing Assembly:

 

Nickel Alloy with PTFE

Load Screw:

 

Bronze Alloy

Towers:

 

Copper Alloy

Pins:

 

Stainless Steel

Deflector:

 

Bronze Alloy

Cup:

 

Steel

Model RFC43 Residential Sprinkler 

SIN RA0612

Page 3 of 7

www.reliablesprinkler.com

Bulletin 006 Rev. K
February 2017

Summary of Contents for RFC Series

Page 1: ...operating ele ment Sprinklers with a 165 F 74 C temperature rating are ordinary temperature classification and should be used with a 135 F 57 C temperature rated cover plate Sprinklers with a 212 F 10...

Page 2: ...essure Max Coverage Area ft x ft m x m Flow gpm l min Pressure psi bar 12x12 3 6x3 6 9 34 9 0 0 62 14x14 4 3x4 3 10 38 11 0 0 76 Table B Model RFC30 Sprinkler Hydraulic Design Criteria Figure 1 Model...

Page 3: ...12x12 3 6x3 6 12 45 7 8 0 54 14x14 4 3x4 3 13 49 9 1 0 63 16x16 4 9x4 9 13 49 9 1 0 63 18x18 5 5x5 5 18 68 17 5 1 21 20x20 6 1x6 1 21 79 23 8 1 64 Table C Model RFC43 Sprinkler Hydraulic Design Crite...

Page 4: ...m l min Pressure psi bar 16x16 4 9x4 9 13 49 0 7 0 0 48 18x18 5 5x5 5 17 64 3 12 0 0 83 20x20 6 1x6 1 20 75 7 16 7 1 15 Table D Model RFC49 Sprinkler Hydraulic Design Criteria Figure 3 Model RFC49 Spr...

Page 5: ...16 60 6 7 6 0 53 18x18 5 5x5 5 18 68 1 9 6 0 66 20x20 6 1x6 1 20 75 7 11 9 0 82 Table E Model RFC58 Sprinkler Hydraulic Design Criteria Figure 4 Model RFC58 Sprinkler Components and Dimensions Sensit...

Page 6: ...t the Model FC wrench over the sprinkler until the wrench engages the body Do not wrench any other part of the sprinkler cup assembly The Model FC wrench is designed to be turned with a standard 1 2 s...

Page 7: ...ock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Prior to installation sprinklers should be maintained in the original cartons and packaging un...

Reviews: