Technical Data:

Nominal K-factor

Thread

Size

   Temperature Rating

Maximum

Ambient

Temperature

Maximum Water 

Working Pressure

Sprinkler Identi

fi

 cation

Number

(SIN)

US

Metric

Sprinkler

Cover

8.0

115

¾” NPT

or ISO 7-R¾

165°F

(74°C)   

135°F

(57°C)

100°F

(38°C)

175 PSI

(12 bar)

RA4762

Coverage Area

Max. Installed

Coverage Area 

Width x Length

De

fl

 ector to Ceiling

Dimension

Min. Required 

Flow Rate

Min. Required 

Pressure

ft. x ft.

m x m

inches

mm

gpm

L/min

psi

bar

14 x 22

4.3 x 6.7

4 - 6

102 - 152

31

117.3

15.0

1,03

14 x 22

4.3 x 6.7

6 - 12

152 - 305

35

132.5

19.1

1,3

14 x 24

4.3 x 7.3

4 - 6

102 - 152

35

132.5

19.1

1,3

14 x 24

4.3 x 7.3 

6 - 12

152 -305

39

147.6

23.8

1,6

16 x 16

4.9 x 4.9

4 - 12

 102 - 305

26

98.4

10.6

0,7

16 x 18

4.9 x 5.5

4 - 12

102 - 305

29

109.8

13.1

0,9

16 x 20

4.9 x 6.1

4 - 12

102 - 305

32

121.1

16.0

1,1

16 x 22

4.9 x 6.7

4 - 12

102 - 305

36

136.2

20.2

1,4

16 x 24

4.9 x 7.3 

4 - 12 

102 - 305

39

147.6

23.8

1,6

18 x 18

5.5 x 5.5

4 - 12

102 - 305

33

124.9

17.0

1,2

18 x 20

5.5 x 6.1

4 - 12

102 - 305

36

136.2

20.2

1,4

18 x 22

5.5 x 6.7

4 - 12

102 - 305

40

151.4

25.0

1,7

Approval Type

Quick Response Extended Coverage - Light Hazard Horizontal Sidewall.
Minimum spacing between sprinklers - 8 feet (2.4m). 
Install below smooth, flat, horizontal ceilings only AS DEFINED BY NFPA 13.

Figure 1

Summary of Contents for G6-80 K8.0

Page 1: ... for a maximum service pressure of 175 psi 12 0 bar Application and Installation The Model G6 80 sprinkler is intended for installation in light hazard occupancies in accordance with NFPA 13 This sprinkler is especially well suited for use in non corrosive environments in student dormitories hotels hospitals and care facilities Model G6 80 Concealed Horizontal Sidewall sprinklers utilize a sprinkl...

Page 2: ...05 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 4 6 102 152 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 6 12 152 305 39 147 6 23 8 1 6 16 x 16 4 9 x 4 9 4 12 102 305 26 98 4 10 6 0 7 16 x 18 4 9 x 5 5 4 12 102 305 29 109 8 13 1 0 9 16 x 20 4 9 x 6 1 4 12 102 305 32 121 1 16 0 1 1 16 x 22 4 9 x 6 7 4 12 102 305 36 136 2 20 2 1 4 16 x 24 4 9 x 7 3 4 12 102 305 39 147 6 23 8 1 6 18 x 18 5 5 x 5 5 4 12 102 305 33 124 ...

Page 3: ...to the sprinkler cup shall be a push on and pull off design al lowing a cover plate adjustment Sprinklers shall have a nominal K factor of 8 0 115 metric Sprinkler temperature rating shall be 165 F 74 C with a cover plate temperature rating of 135 F 57 C Sprinklers shall be capable of a max imum coverage area of 16 ft x 24 ft 4 9 m x 7 4 m or 18 ft x 22 ft 5 5 m x 6 7 m with a minimum lateral spac...

Page 4: ...roughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrica...

Reviews: