Maintenance

Model G6-80 Concealed Sprinklers should be inspected 

and maintained in accordance with NFPA 25.  Do not clean 
sprinklers with soap and water, ammonia or any other clean-
ing fluids.  Remove dust by using a soft brush or gentle 
vacuuming.  Replace any sprinkler or cover plate assem-
bly, which has been painted (other than factory applied) or 
damaged in any way.  A stock of spare sprinkler and cover 
plate assemblies should be maintained to allow quick re-
placement of damaged or operated sprinklers.  Prior to in-
stallation, sprinklers should be maintained in their original 
cartons and packaging until used to minimize the potential 
for damage to sprinklers that would cause improper opera-
tion or non-operation.

Model G6-80 Concealed Quick Response
Extended Coverage Light Hazard Horizontal 
Sidewall Sprinkler Speci

fi

 cation

Sprinklers shall be quick-response extended coverage 

sprinklers that are cULus Listed for use in Light Hazard oc-
cupancies. Sprinklers to be of bronze frame construction 
with brass cover plate and copper alloy retainer flange as-
sembly. Water seal assembly shall consist of a PTFE coated 
Belleville spring washer and machined brass cup contain-
ing no plastic parts. Method of attaching the cover plate to 
the sprinkler cup shall be a push-on and pull-off design al-
lowing a ¼” cover plate adjustment.  Sprinklers shall have a 
nominal K-factor of 8.0 (115 metric).  Sprinkler temperature 
rating shall be 165°F (74°C) with a cover plate temperature 
rating of 135°F (57°C).  Sprinklers shall be capable of a max-
imum coverage area of 16 ft. x 24 ft. (4.9 m x 7.4 m) or 18 
ft. x 22 ft (5.5 m x 6.7 m), with a minimum lateral spacing of 
8 ft. (2.4 m).  Rated working pressure shall be 175 psi (12,0 
bar).  A plastic protective cap shall be provided and fac-
tory installed inside the sprinkler cup to protect the sprinkler 
from damage, which could occur during construction before 
the cover plate is installed. Installation threads shall be [1-
inch NPT] [ISO 7-R¾]. Cover plate finish: [Chrome] [White] 
[Custom Color– specify]. Extended Coverage Concealed 
horizontal sidewall sprinklers shall be Reliable Model G6-80. 
SIN RA4762 (Bulletin 047).

Ordering Information

Specify:

1.  Sprinkler: Model G6-80
2.  Cover Plate Type: Solid or Perforated
3.  Cover Plate Finish

Installation Wrench

Model G6 Sprinkler Wrench

Installation Aid

A protective plastic cap is included for use during instal-
lation. 

Cover Plate Finishes

(1)

Standard Finishes

Chrome

White Paint

Special Application Finishes

Bronze
Black Paint
Flat White Paint

(1)

 Other colors and finishes are available.  Consult factory for details.

Note:

 Paint or any other coatings applied over the factory 

finish will void all approvals and warranties.

Summary of Contents for G6-80 K8.0

Page 1: ... for a maximum service pressure of 175 psi 12 0 bar Application and Installation The Model G6 80 sprinkler is intended for installation in light hazard occupancies in accordance with NFPA 13 This sprinkler is especially well suited for use in non corrosive environments in student dormitories hotels hospitals and care facilities Model G6 80 Concealed Horizontal Sidewall sprinklers utilize a sprinkl...

Page 2: ...05 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 4 6 102 152 35 132 5 19 1 1 3 14 x 24 4 3 x 7 3 6 12 152 305 39 147 6 23 8 1 6 16 x 16 4 9 x 4 9 4 12 102 305 26 98 4 10 6 0 7 16 x 18 4 9 x 5 5 4 12 102 305 29 109 8 13 1 0 9 16 x 20 4 9 x 6 1 4 12 102 305 32 121 1 16 0 1 1 16 x 22 4 9 x 6 7 4 12 102 305 36 136 2 20 2 1 4 16 x 24 4 9 x 7 3 4 12 102 305 39 147 6 23 8 1 6 18 x 18 5 5 x 5 5 4 12 102 305 33 124 ...

Page 3: ...to the sprinkler cup shall be a push on and pull off design al lowing a cover plate adjustment Sprinklers shall have a nominal K factor of 8 0 115 metric Sprinkler temperature rating shall be 165 F 74 C with a cover plate temperature rating of 135 F 57 C Sprinklers shall be capable of a max imum coverage area of 16 ft x 24 ft 4 9 m x 7 4 m or 18 ft x 22 ft 5 5 m x 6 7 m with a minimum lateral spac...

Page 4: ...roughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrica...

Reviews: