Maintenance

The Model G5-56 Dry should be inspected and the sprin-

kler system maintained in accordance with NFPA 25. Do not 
clean sprinklers with soap and water, ammonia or any other 
cleaning fluids. Replace any sprinkler that has been painted 
(other than factory applied) or damaged in any way. Con-

cealed sprinklers cover plates can not be painted in the field, 

after installation or have any other coating applied other than 

the factory finish. A stock of spare sprinklers should be main

-

tained to allow quick replacement of damaged or operated 
sprinklers. Prior to installation, sprinkler should be maintained 
in the original cartons and packaging to minimize the potential 
for damage to sprinklers that would cause improper operation 
or non-operation.

Engineering Specification

Model G5-56 Dry Pendent Concealed Sprinkler

Dry pendent sprinklers shall be dry pendent concealed sprin-

klers with a flat cover plate. Sprinklers shall be cULus Listed as 
Quick Response for Light and Ordinary Hazard applications 
as well as FM Approved as Standard Response. Sprinklers 
shall be available in lengths from 4¼ inches (108mm) to 48 
inches (1219mm) in ¼-inch (6.35mm) increments based on 

face of fitting to finished ceiling distance. Sprinkler length shall 

be selected to provide the Exposed Minimum Barrel Length 
based on the minimum design temperature in the protected 
area and the minimum temperature in the conditioned space 
where the barrel is located in accordance with the Manufac-
turer’s written installation instructions. Sprinklers shall have 

[1-inch NPT][ISO 7-1 R1] threaded inlet fittings with [standard 

length inlets designed for use with wet- or dry-pipe sprinkler 

systems][short  length  inlets  designed  for  use  with  wet-pipe 
sprinkler  systems  having  pipe  fittings  with  internal  obstruc

-

tions that prevent the insertion of standard length inlets].  
Sprinklers shall have a PTFE coated beryllium nickel Belleville 
spring washer inlet seal and brass alloy cap that prevent water 
entry from the sprinkler system piping into the sprinkler prior 
to actuation. Sprinklers shall have a fast-response fusible link 
that controls the movement of the inlet seal and cap through 
a mechanism consisting of link arms, a seat adapter, an ori-

fice adapter, an inner tube, and a yoke. Sprinklers shall use 

a drop down deflector supported by tapered pins. Sprinklers 
shall have a galvanized steel cup for threaded attachment of 
the flat cover plate assembly. Cover plate attachment shall 
provide up to ½-inch (13mm) of adjustment. Sprinklers shall 

be  [Ordinary  temperature  classification,  165°F  (74°C),  with 
135°F temperature rated cover plates][Intermediate tempera

-

ture classification, 212°F, with 165°F temperature rated cover 
plates]. Cover plates shall be [solid][perforated] with factory 
applied [White][Chrome][Special Application – Specify] finish. 

Dry pendent concealed sprinklers shall be Reliable Model G5-
56 Dry (SIN RA5114). 

Ordering Information

Specify:

1.  Sprinkler: Model G5-56 Dry
2. 

Threads: [1-inch NPT - standard][ISO 7/1 R1 - optional]

3. 

Inlet  Length:  [Standard][Short  (“PL”)–  for  existing  wet-

pipe installations only]

4. 

Cover Plate Finish: [White][Chrome][Special Application 

– Specify]

5. 

Sprinkler/Cover  Plate  Temperature  Rating:  [Ordinary  – 
165°F  sprinkler  with  135°F  cover  plate][Intermediate  – 

212°F sprinkler with 165°F cover plate]

6. 

Nominal Sprinkler Length (face of fitting to face of ceiling 
- “A” Dimension from Fig. 1): [Specify length – Lengths 

available from 4¼ inches to 48 inches (108mm to 
1219mm) in ¼-inch (6.35mm) increments]

6.