background image

Optional Cover Plate with Gasket*

Model G4/G5 

QR Gasket

Cover Plate

(cULus Listed)

Model G4/G5 SR Gasket

Cover Plate

(FM Approved)

* Model G4/G5 QR Gasket and Model G4/G5 SR Gasket cover 
plates are sold as assembled units including both the cover plate 
and gasket. Model G4 /G5 QR Gasket and Model G4 /G5 SR Gas-
ket cover plates and gaskets are not interchangeable.

Installation Instructions

   When used on wet pipe systems, Reliable Model G5-56 

dry pendent sprinklers may be installed in ductile or malleable 
cast iron threaded tees, or CPVC tees and adapters upon veri-

fication that the sprinkler inlet fitting does not interfere with the 
interior of the fitting (see Figure 3). 

   When used on dry pipe systems, Reliable Model G5-56 dry 

pendent sprinklers MUST ONLY BE installed in the outlets of 
ductile or malleable cast iron threaded tees on horizontal pipe 
such that the inlet of the sprinkler protrudes above the bottom 
level of the pipe. 

   DO NOT install Reliable dry sprinklers into elbows or cou-

plings, welded outlets, mechanical tees, or gasket sealed 

CPVC fittings.

   Dry sprinklers connected to wet pipe systems must be in-

stalled as indicated in Figure 2 and as required by NFPA 13 with 
the Exposed Minimum Barrel Length located in a heated area.

   DO NOT install the Reliable Model G5-56 dry pendent sprin-

kler in ceilings that have positive pressure in the space above.

The following steps must be followed for 
installation:

1.  Cut a 2

5

/

8

-inch (67mm) diameter hole in the ceiling directly 

in-line with the outlet of the tee. 

2.  Apply pipe joint compound or Polytetrafluoroethylene 

(PTFE) tape to the threads of the sprinkler’s inlet fitting.

3.  A protective cap is provided to protect the drop-down 

sprinkler deflector from damage which could occur during 
construction before the cover plate is installed. The cap is 
factory installed inside the sprinkler cup. Remove the cap 
to install sprinkler, Step 4, then reinstall cap until the cover 
plate is installed.

4.  Install the sprinkler in the tee using the Model FC wrench. 

The Model FC wrench has a socket drive which is inserted 
into the sprinkler’s cup and around the body of the sprinkler 
prior to installation of the sprinkler. Do NOT wrench any of 
the part of the sprinkler/cup assembly. The sprinkler is then 

tightened into the pipe fitting to achieve a leak free connec

-

tion. The recommended minimum to maximum installation 
torque is 22-30 lb-ft (30 – 40 N-m). When inserting or re-
moving the wrench from the sprinkler/cup assembly, care 
should be taken to prevent damage to the sprinkler. Rein-
stall the protective cap following installation of the sprinkler, 
until the cover plate is installed.
a.  Alternatively, where access to the outer tube of the 

sprinkler is available, the Model G5-56 Dry sprinkler 
may be installed using a pipe wrench. The protec-
tive cap should not be removed to install the sprin-
kler with a pipe wrench. The pipe wrench shall only 
be permitted to interface with the steel outer tube 
portion of the sprinkler (Item #8 in Fig. 4). Do NOT 
wrench any other portion of the sprinkler/cup as-
sembly. A pipe wrench can install the sprinkler into 

the fitting with a large amount of torque; consider

-

ation should be given to the need for future removal 
of the sprinklers because the installation torque will 
have to be matched or exceeded to remove the 
sprinkler. The recommended minimum to maximum 
installation torque is 22-30 lb-ft (30 – 40 N-m).

5.  To install the cover plate, remove the protective cap and in-

stall the cover plate by hand turning the cover in the clock-
wise direction until it is tight against the ceiling.  For Model 
G4 /G5 QR Gasket and Model G4 /G5 SR Gasket cover 
plates, the gasket should be attached to the flange of the 
cover plate skirt only. Do not glue the gasket in place or 
allow the gasket to overlap both the cover plate and the 
flange of the skirt.

Model FC

Sprinkler Wrench

3.

Cover Plate Finishes

Standard Finishes

White Paint
Chrome

Special Application
Finishes

Off White Paint
Black Paint
Custom Color Paint – Specify

(1)

Raw Brass (Lacquered)
Bright Brass
Finished Bronze
Black Plated
Satin Chrome
Stainless Steel Clad

(2)

(1)

  Custom color paint is semi-gloss, unless specified otherwise.

(2)

  Stainless steel clad cover plates are Type 316 Stainless Steel on the finished 

side and C102 Copper Alloy on the back side. Cover plates are not listed or ap-
proved as corrosion resistant. Stainless steel clad cover plates are not available 
perforated.

Reviews: