Model F1FR56-300 Quick Response Extended Coverage Pendent Sprinkler 

Deflector: 

QREC

Installation Wrench: 

Model D Sprinkler Wrench or Model W2 Sprinkler Wrench

Approval Type: 

Quick Response Extended Coverage - Light Hazard Occupancy

Model F1FR56-300 Quick Response Extended Coverage Recessed Pendent Sprinkler

Deflector: 

QREC

Installation Wrench: 

Model GFR2 Sprinkler Wrench

 

Approval Type: 

Quick Response

 

Extended Coverage - Light Hazard Occupancy

(1)

 When installed directly into a tee, the escutcheon adjustment will be 

reduced.

(2)

 Refer to escutcheon data table for dimensions.

Installation Data:

Nominal 

Orifice

Thread 

Size

“K” Factor

Sprinkler 

Length

Temperature

Rating

Sprinkler

Identification 

Numbers (SIN)

US

Metric

°F

°C

½” 

(15mm)

½” NPT 

(R1/2)

5.6

80

2.25” 

(57mm)

135
155

57

 68

RA3045

Table 1

Coverage Area

Flow Rate

Pressure

K=5.6 (80)

Max. Coverage Area

Width x Length

gpm

L/min

psi

bar

ft. x ft.

m x m

26
33
40

98.4

124.9
151.5

21.6
34.7
51.0

 1,5

2,4
3,5

16 x 16
18 x 18
20 x 20

4.9 x 4.9
5.5 x 5.5

6.0 x 6.0

(1)

(1)

 135°F (57°C) only.

Installation Data

(1)

:

Nominal 

Orifice

Thread

Size

“K” Factor

Sprinkler

Length

Temperature

Rating

Sprinkler

Identification

Numbers (SIN)

US

Metric

°F

°C

½” 

(15mm)

½” NPT 

(R1/2)

5.6

80

2.25” 

(57mm)

135
155

57
68

R3045

(1)

 For Coverage Area refer to Table 1.

QREC Pendent

Model F156-300 EC F1/F2

Model F156-300 EC FP

Fig. 1

Fig. 2