The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588
Sales Offices
(800) 848-6051
Sales Fax
(914) 829-2042
Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 03/17
P/N 9999970390
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years.
Finishes
(1)
Standard Finishes
Sprinkler
Escutcheon
Bronze
Chrome Plated
White Polyester Coated
Brass
Chrome Plated
White Painted
Special Application Finishes
Sprinkler
Escutcheon
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
Cover Plate Finishes
(1)
Standard Finishes
Chrome
White
Special Application Finishes
Bright Brass
Black Plating
Black Paint
Off White
(1)
Other colors and finishes are available on special order. Consult
factory for details. Coverplate custom paint is semi-gloss, unless
specified otherwise.
Note:
Paint or any other coating applied over the factory finish will void
approvals and waranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover Plate Model
10. Cover Plate Thread Size
11. Cover Plate Temperature Rating
12. Cover Plate Adjustment
13. Cover Plate Finish
Note:
When F1FR56-300 QREC Recessed sprinklers are ordered, the sprin-
klers, escutcheons and coverplates are packaged separately.
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model F1FR56-
300 QREC Pendent Sprinkler or the use of the Model CCP
concealed cover plate assembly on any sprinkler with
which it is not specifically listed may prevent good fire
protection and will void all guarantees, warranties, listings
and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Maintenance
Model F1FR56-300 QREC Sprinklers should be inspect-
ed and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by us-
ing a soft brush or gentle vacuuming. Remove any sprin-
kler that has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damage or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Escutcheon Data:
Escutcheon
Model
Adjustment
“A”
Dimension
Face of Fitting to Ceiling
or Wall Dimension
F1
Max Recess
Min Recess
1½” (38.1mm)
3
/
4
” (19.1mm)
3
/
16
” -
15
/
16
”
(5mm - 24mm)
F2
Max Recess
Min Recess
1 ½” (38.1mm)
1” (24mm)
3
/
16
” -
11
/
16
”
(5mm - 17mm)
FP Push-on/
Thread-off
Max Recessed
Min Recessed
7
/
16
” (11mm)
15
/
16
(24mm)
1
1
/
2
” (38.1mm)
1” (25.4mm)
Maximum Working Pressure
300 psi (20.7 bar)
100% Factory tested hydrostatically to 600 psi (41.4 bar)