Coverage Area

Flow Rate

gpm (L/m)

Pressure

psi (bar)

Max. Coverage Area 

Width x Length

ft. x ft. (m x m)

K=5.6 (Metric 80)

21.2 (80.3)

26 (98.4)

33 (124.9)
40 (151.5) 

14.2 (0,98)

21.6 (1,5)
34.7 (2,4)
51.0 (3,5)

14 x 14 (4.3 x 4.3)
16 x 16 (4.9 x 4.9)
18 x 18 (5.5 x 5.5)

20 x 20

(1)

 (6.0 x 6.0)

(1)

(1)

 135°F (57°C) Only

Thread

Size

Model

Temp. Rating

Max.

Ambient

Temp.

Bulb

Color

Sprinkler Cover

½” NPT

(R1/2)

F1FR-300

QREC

135°F

57°C

135°F

57°C

100°F 

38°C

Orange

½” NPT

(R1/2)

F1FR-300

QREC

155°F

68°C

135°C

57°C

100°F

38°C

Red

Technical Data:

Nominal

Orifice

Thread

Size

“K” Factor

Sprinkler

Identification

Number (SIN)

US Metric

½” 

(15mm)

½”

(R1/2)

5.6

80

RA3045

Model F1FR56-300 Quick Response Extended Coverage Concealed Pendent Sprinkler

Installation Wrench: 

Model RC1 Sprinkler Wrench

 

Approval Type: 

Quick Response

 

Extended Coverage - Light Hazard Occupancy

3.

Installation Aid:

A protective cap is included for use during installation.

Installation

Quick response sprinklers are intended for installation 

as specified in NFPA 13.  Quick response sprinklers and 
standard response sprinklers should not be intermixed.

The Model F1FR56-300 QREC Pendent and Recessed 

Sprinklers are to be installed as illustrated.  The Model F1, 
F2, and FP  escutcheons illustrated are the only recessed 
escutcheons to be used with the these sprinklers.  The use 
of any other recessed escutcheon will void all approvals 
and negate all warranties.

When installing Model F1FR56-300 QREC Pendent 

Sprinklers, use the Model D Sprinkler Wrench or Model 
W2 Sprinkler Wrench.  When installing F1FR56-300 QREC 
Recessed Pendent Sprinkler, use the Model GFR2 Sprin-
kler Wrench.  Any other type of wrench may damage these 
sprinklers.

Model F1FR56-300 QREC Concealed Sprinklers use 

135°F (57°C) or 155°F (68°C) Model F1FR56-300 QREC 
Pendent Sprinklers with a threaded Model CCP cup which 
is factory attached to the sprinkler.  The assembly is com-
pleted by the installation of the attractive, low profile, 135°F 
(57°C) rated cover plate assembly.  The cover plate and 
sprinkler cup are joined using a flexible tooth threaded en-
gagement.  A choice of two cover plate assemblies pro-
vides either ½” (13mm) or 5/16” (8mm) of cover adjust-

ment.

Do not install these sprinklers in ceilings which have pos-

itive pressure in the space above.

After a 2

5

/

8

” (67mm) inch diameter hole is cut in the ceil-

ing, the sprinkler is easily installed with the Model RC1 
Wrench.  When installing a sprinkler, the protective cap 
is removed and the wrench is positioned into the sprin-
kler/cup assembly until the two wrench faces engage the 
wrenching flats on the Model F1FR56 QREC Sprinkler.  
The sprinkler is then tightened into the pipe fitting. When 
inserting or removing the wrench from the sprinkler/cup 
assembly, care should be taken to prevent damage to 
the sprinkler.  DO NOT WRENCH ON  ANY OTHER PART 
OF THE SPRINKLER. The cover plate assembly is then  
pressed into the cup.  Final adjustment is made by turning 
the cover plate until the skirt flange makes full contact with 
he ceiling surface. Cover plate removal requires turning in 
the counter clockwise direction. 

After installation, inspect all sprinklers to ensure that 

there is a  gap between the cover plate and ceiling and 
that the four cup slots are open and free from any air flow 

Fig. 3

Fig. 4