background image

Model F1 Res 30 LL, 49 LL & 58 LL CCP Pendent 
(Concealed) Specifications

Sprinklers shall be [cULus Listed] [WaterMark Certified 

WMCS] low flow residential concealed sprinklers engi-
neered to provide a minimum design density of 0.05 gpm/
ft

2

 over the listed coverage area.   Listed flows as speci-

fied by the manufacturer’s technical data sheets are to be 
used. Residential sprinklers shall be installed in confor-
mance with the manufacturer’s installation guidelines and 
the applicable installation standard. Sprinkler frame and 
deflector shall be of bronze frame construction having a ½” 
NPT thread.  Water seal assembly shall consist of a PTFE-
coated Belleville spring washer with top-loaded extruded 
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of 155°F (68°C).  
Cover plate assembly shall consist of a brass cover plate 
and copper alloy retainer flange.  Method of attaching the 
cover plate to the sprinkler cup shall be a push-on and 
thread-off design allowing a ½” cover plate adjustment.  
Cover plate temperature rating shall be 135°F (57°C).  A 
plastic protective cap shall be provided and factory in-
stalled inside the sprinkler cup to protect the sprinkler from 
damage, which could occur during construction before the 
cover plate is installed. Standard cover plate finish: [White] 
[Custom Color– specify]. ]. Concealed pendent sprinklers 
shall be Reliable Model F1 Res 30 LL, 49 LL & 58 LL CCP, 
SIN RA3311, RA3316 & RA3313 (Bulletin 033).

Model F1 Res 44 LL Horizontal Sidewall
Residential Sprinkler Specifications

Sprinklers shall be [cULus Listed] [WaterMark Certified 

WMCS] low flow residential horizontal sidewall sprinklers 
engineered to provide a minimum design density of 0.05 
gpm/ft

2

 over the listed coverage area.   Listed flows as 

specified by the manufacturer’s technical data sheets are to 
be used.  Residential sprinklers shall be installed in confor-
mance with the manufacturer’s installation guidelines and 
the applicable installation standard.  Sprinkler frame and 
deflector shall be of bronze frame construction having a ½” 
NPT thread.  Water seal assembly shall consist of a PTFE-
coated Belleville spring washer with  top-loaded extruded 
or cold head cup with 3 mm glass bulb containing no plas-
tic parts, and having a temperature rating of [155°F (68°C)] 
[175°F (79°C)].  Sprinklers shall have a nominal K-factor 
of 4.4 (62.8).  Standard finish: [Bronze] [Chrome-plated] 
[White Polyester] [Special finish– specify]. Residential hori-
zontal sidewall sprinklers shall be Reliable Model F1 Res 
44 LL, SIN RA3331 (Bulletin 033).

Model F1 Res 44 LL Recessed 
Horizontal Sidewall Sprinkler

 

Specifications

Use description for the Model F1 Res 44 horizontal side-

wall sprinkler with the following modifications:  Replace 
“horizontal sidewall sprinkler” with “recessed horizontal 
sprinkler.”  Add:  Recessed escutcheon assembly shall be 
a steel, two-piece escutcheon with ½” adjustment (Model 
F2). Standard finish shall be [brass][bright chrome] [white 
painted] [Special finish– specify]. Residential recessed 
horizontal sidewall sprinklers shall be Reliable Model F1 
Res 44 LL/F2, SIN RA3331 (Bulletin 033).

Standard Finishes

Sprinkler

F1, F2, FP 

Escutcheons

Cover Plates

Bronze
Chrome Plated
White and Black Polyester 
Coated 

Brass
Bright Chrome Plated 
White Painted

White Painted
Chrome

Special Application Finishes

Sprinkler

F1, F2,

Escutcheons

Cover Plates

Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome

Bright Brass
 Black Plated
Black Paint
Off White
Satin Chrome

Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome

(1)

 Other finishes and colors are available on special order.  

    Consult factory for details.

Note:

  Paint or any other coating applied over the factory finish will void 

all approvals and warranties.

Ordering Information

Specify:

1.  Sprinkler Model
2.  Sprinkler Type
3.  Temperature Rating
4.  Sprinkler Finish
5.  Escutcheon Finish
6.  Cover Plate Finish

Reliable Automatic Sprinkler Co., Inc.

(800) 431-1588    

Sales Offices

(800) 848-6051    

Sales Fax

(914) 829-2042    

Corporate Offices

www.reliablesprinkler.com   Internet Address

Manufactured by

Recycled

Paper 

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 02/19

P/N 9999970411

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.

Summary of Contents for F1 Res 30 LL

Page 1: ...L Recessed Pendent FP F1Res49LL 58LLRecessed Pendent F1 F1 Res 30 LL Recessed Pendent F2 F1 Res 44 LL 58 LL Recessed HSW F2 F1 Res 30 LL 49 LL 58 LL CCP Pendent F1 Res 44 LL SWC Product Description Model F1 Res LL Pendent sprinklers Figs 1 2 3 4 are fast response sprinklers combining excellent durability high sensitivity glass bulb and low profile decorative design The F1 Res LL Horizontal Sidewal...

Page 2: ...el F1 Res LL sprinklers Use of any other recessed escutcheon will void all approvals and warranties For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin kler Wrench for installing Models F1 Res LL Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench Use o...

Page 3: ... 79 100 150 38 66 4 9 70 6 2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 13 49 7 0 0 48 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or ...

Page 4: ...2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 61 7 6 0 53 16 61 7 6 0 53 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3...

Page 5: ... Ft m Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 Smooth Ceilings 1 2 to 1 13mm to 25mm using CCP or FP escutcheon Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3 14 4 3 13 49 7 0 0 48 16 x 16 4 9 x 4 9 16 4 9 14 53 8 2 0 56 18 x 18 5 5 x 5 5 18 5 5 18 68 1 13 5 0 93 20 x 20 6 1 x 6 1 20 6 1 20 75 7 16 7 1 14 Note Sprinklers shown in Fig 3 and Fig 4 are n...

Page 6: ...nch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 12 45 4 7 5 0 52 12 45 4 7 5 0 52 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 14 53 0 10 2 0 71 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 16 4 9 16 60 6 13 3 0 92 16 60 6 13 3 0 92 16 x 18 4 9 x 5 5 16 4 9 18 68 1 16 8 0 53 18 68 1 16 8 0 53 18 x 18 5 5 x 5 5 18 5 5 19 72 0 18 7 1 29...

Page 7: ...Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 60 6 7 6 0 53 16 60 6 7 6 0 53 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 18 68 2 9 7 0 69 18 68 2 9 7 0 69 16 x 16 4 9 x 4 9 16 4 9 21 79 5 13 2 0 91 21 79 5 13 2 0 91 16 x 18 4 9 x 5 5...

Page 8: ...del F1 Res 30 LL 49 LL 58 LL Recessed Pendent FP Specifications Sprinklers shall be cULus Listed WaterMark Certified WMCS low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0 05 gpm ft2 over the listed coverage area Listed flows as specified by the manufacturer s technical data sheets are to be used Residential sprinklers shall be installed in con fo...

Page 9: ...ld head cup with 3 mm glass bulb containing no plas tic parts and having a temperature rating of 155 F 68 C 175 F 79 C Sprinklers shall have a nominal K factor of 4 4 62 8 Standard finish Bronze Chrome plated White Polyester Special finish specify Residential hori zontal sidewall sprinklers shall be Reliable Model F1 Res 44 LL SIN RA3331 Bulletin 033 Model F1 Res 44 LL Recessed Horizontal Sidewall...

Reviews: