Maintenance

Model F1 Res 30 LL, 49 LL, F1 Res 58 LL and F1 Res 44  

LL Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D, and 
13R.  Do not clean sprinkler with soap and water, Ammonia 
or any other cleaning fluids. Remove dust by using a soft 
brush or gentle vacuuming. Replace any sprinkler which 
has been painted (other than factory applied) or damaged 
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or operated 
sprinklers. Prior to installation, sprinklers should remain 
in the original cartons and packaging until used. This will 
minimize the potential for damage to sprinklers that could 
cause improper operation or non-operation.

Model F1 Res 30 LL, 49 LL & 58 LL Pendent
Sprinkler Specifications

Sprinklers shall be [cULus Listed] [WaterMark Certified 

WMCS] low flow residential pendent sprinklers engineered 
to provide a minimum design density of 0.05 gpm/ft

2

 over 

the listed coverage area.   Listed flows as specified by the 
manufacturer’s technical data sheets are to be used.  Resi-
dential sprinklers shall be installed in conformance with the 
manufacturer’s installation guidelines and the applicable 
installation standard.  Deflector-to-ceiling distance listing 
shall be 1” to 4” maximum, unless specifically listed other-
wise. Sprinkler frame and deflector shall be of bronze frame 
construction having a ½” NPT thread.  Water seal assembly 
shall consist of a PTFE-coated Belleville spring washer with 
top-loaded extruded or cold head cup with 3 mm glass 
bulb containing no plastic parts, and having a temperature 
rating of [155°F (68°C)] [175°F (79°C)].  Sprinklers shall 
have a nominal K-factor of 3.0, 4.9 and 5.8.  Standard fin-
ish: [Bronze] [Chrome-plated] [White Polyester] [Special 
finish– specify]. Residential pendent sprinklers shall be 
Reliable Model F1 Res 30 LL, 49 LL & 58 LL, SIN RA3311, 
RA3316 & RA3313 (Bulletin 033).

Model F1 Res 49 LL & 58 LL Recessed 
Pendent/F1 
Model F1 Res 30 LL, 49 LL & 58 LL Recessed 
Pendent/F2 
Model F1 Res 30 LL, 49 LL & 58 LL Recessed 
Pendent/FP Specifications

Sprinklers shall be [cULus Listed] [WaterMark Certified 

WMCS] low flow residential recessed pendent sprinklers 
engineered to provide a minimum design density of 0.05 
gpm/ft

2

 over the listed coverage area.   Listed flows as 

specified by the manufacturer’s technical data sheets are 
to be used.  Residential sprinklers shall be installed in con-
formance with the manufacturer’s installation guidelines 
and the applicable installation standard.  Deflector-to-ceil-
ing distance listing shall be 1” to 4” maximum, unless spe-
cifically listed otherwise. Sprinkler frame and deflector shall 
be of bronze frame construction having a ½” NPT thread.  
Water seal assembly shall consist of a PTFE-coated Bel-
leville spring washer with top-loaded extruded or cold 
head cup with 3 mm glass bulb containing no plastic parts, 
and having a temperature rating of [155°F (68°C)] [175°F 
(79°C)].  Sprinklers shall have a nominal K-factor of 3.0, 4.9 
& 5.8.  Standard finish: [Bronze] [Chrome-plated] [White 
Polyester] [Special finish– specify].  Recessed escutcheon 
assembly shall be a steel, two-piece escutcheon [with ½” 
adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of 
push-on and thread off design with ½” adjustment (Model 
FP)]. Standard finish shall be [brass][bright chrome] [white 
painted].  Residential recessed pendent sprinklers shall be 
Reliable [Model F1 Res 30 LL, 49 LL & 58 LL Recessed 
Pendent/F1] [Model F1 Res 30 LL, 49 LL & 58 LL Recessed 
Pendent/F2] [Model F1 Res 30 LL, 49 LL & 58 LL Recessed 
Pendent/FP] SIN RA3311, RA3316 & RA3313 (Bulletin 033).

8.

Max. Coverage area 

Ft x Ft (m x m)

Max. Spacing 

Ft (m)

Ordinary Temp. Rating 

(155°F/68°C)

Top of Deflector to 

Ceiling

Inch (mm)

Minimum 

Spacing

Ft (m)

Flow

GPM (L/min)

Pressure

PSI (bar)

12 x 12 (3.6 x 3.6)

12 (3.6)

13 (49.2)

8.7 (0.60)

4 to 6 (100 to 152)

8 (2.4)

14 x 14 (4.3 x 4.3)

14 (4.3)

14 (53.0)

10.2 (0.71)

16 x 16 (4.9 x 4.9)

16 (4.9)

17 (64.3)

15.0 (1.1)

16 x 18 (4.9 x 5.5)

16 (4.9)

19 (71.8)

18.7 (1.13)

16 x 20 (4.9 x 6.1)

16 (4.9)

23 (87.1)

27.4 (1.89)

12 x 12 (3.6 x 3.6)

12 (3.6)

14 (52.9)

10.2 (0.71)

6 to 12 (152 to 305)

14 x 14 (4.3 x 4.3)

14 (4.3)

15 (56.7)

11.7 (0.81)

16 x 16 (4.9 x 4.9)

16 (4.9)

18 (68.1)

16.8 (1.16)

16 x 18 (4.9 x 5.5)

16 (4.9)

20 (75.6)

20.7 (1.43)

Technical Data: F1Res 44 LL SWC (SIN RA3331) continued

Summary of Contents for F1 Res 30 LL

Page 1: ...L Recessed Pendent FP F1Res49LL 58LLRecessed Pendent F1 F1 Res 30 LL Recessed Pendent F2 F1 Res 44 LL 58 LL Recessed HSW F2 F1 Res 30 LL 49 LL 58 LL CCP Pendent F1 Res 44 LL SWC Product Description Model F1 Res LL Pendent sprinklers Figs 1 2 3 4 are fast response sprinklers combining excellent durability high sensitivity glass bulb and low profile decorative design The F1 Res LL Horizontal Sidewal...

Page 2: ...el F1 Res LL sprinklers Use of any other recessed escutcheon will void all approvals and warranties For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin kler Wrench for installing Models F1 Res LL Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench Use o...

Page 3: ... 79 100 150 38 66 4 9 70 6 2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 13 49 7 0 0 48 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or ...

Page 4: ...2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 61 7 6 0 53 16 61 7 6 0 53 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3...

Page 5: ... Ft m Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 Smooth Ceilings 1 2 to 1 13mm to 25mm using CCP or FP escutcheon Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3 14 4 3 13 49 7 0 0 48 16 x 16 4 9 x 4 9 16 4 9 14 53 8 2 0 56 18 x 18 5 5 x 5 5 18 5 5 18 68 1 13 5 0 93 20 x 20 6 1 x 6 1 20 6 1 20 75 7 16 7 1 14 Note Sprinklers shown in Fig 3 and Fig 4 are n...

Page 6: ...nch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 12 45 4 7 5 0 52 12 45 4 7 5 0 52 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 14 53 0 10 2 0 71 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 16 4 9 16 60 6 13 3 0 92 16 60 6 13 3 0 92 16 x 18 4 9 x 5 5 16 4 9 18 68 1 16 8 0 53 18 68 1 16 8 0 53 18 x 18 5 5 x 5 5 18 5 5 19 72 0 18 7 1 29...

Page 7: ...Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 60 6 7 6 0 53 16 60 6 7 6 0 53 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 18 68 2 9 7 0 69 18 68 2 9 7 0 69 16 x 16 4 9 x 4 9 16 4 9 21 79 5 13 2 0 91 21 79 5 13 2 0 91 16 x 18 4 9 x 5 5...

Page 8: ...del F1 Res 30 LL 49 LL 58 LL Recessed Pendent FP Specifications Sprinklers shall be cULus Listed WaterMark Certified WMCS low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0 05 gpm ft2 over the listed coverage area Listed flows as specified by the manufacturer s technical data sheets are to be used Residential sprinklers shall be installed in con fo...

Page 9: ...ld head cup with 3 mm glass bulb containing no plas tic parts and having a temperature rating of 155 F 68 C 175 F 79 C Sprinklers shall have a nominal K factor of 4 4 62 8 Standard finish Bronze Chrome plated White Polyester Special finish specify Residential hori zontal sidewall sprinklers shall be Reliable Model F1 Res 44 LL SIN RA3331 Bulletin 033 Model F1 Res 44 LL Recessed Horizontal Sidewall...

Reviews: