background image

7.

Technical Data: F1Res 44 LL SWC (SIN RA3331)

Thread

Size

Nominal

Orifice

Inch (mm)

Max.

Pressure

psi (bar)

Cover 
Temp.

Rating

Max.

Ambient 

Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

½” NPT 

(R½)

3

/

8

” (10)

175 (12)

135

57

100

38

4.4 (63)

2.45 (62)

• 

Model F1 Res 44 LL SWC

Fig. 6

Technical Data: F1Res 58 LL HSW & HSW/F2 (SIN RA3333)

Thread

Size

Nominal

Orifice

Inch (mm)

Max.

Pressure

psi (bar)

Sprinkler

Temp. Rating

Max.

Ambient 

Temp.

K

Factor

Sprinkler

Length

Inch (mm)

°F

°C

°F

°C

½” NPT 

(R½)

1

/

2

” (13)

175 (12)

155
175

68
79

100
150

38
66

5.8 (83.5)

2.45 (62)

Max. Coverage area 

Ft x Ft (m x m)

Max. Spacing 

Ft (m)

Ordinary Temp. Rating 

(155°F/68°C)

Intermediate  Temp. Rating 

(175°F/79°C)

Top of Deflector to 

Ceiling

Inch (mm)

Minimum 

Spacing

Ft (m)

Flow

GPM (L/min)

Pressure

PSI (bar)

Flow

GPM (L/min)

Pressure

PSI (bar)

12 x 12 (3.6 x 3.6)

12 (3.6)

16 (60.6)

7.6 (0.53)

16 (60.6)

7.6 (0.53)

4 to 6 (100 to 152)

8 (2.4)

14 x 14 (4.3 x 4.3)

14 (4.3)

18 (68.2)

9.7 (0.69)

18 (68.2)

9.7 (0.69)

16 x 16 (4.9 x 4.9)

16 (4.9)

21 (79.5)

13.2 (0.91)

21 (79.5)

13.2 (0.91)

16 x 18 (4.9 x 5.5)

16 (4.9)

25 (94.7)

18.6 (1.28)

25 (94.7)

18.6 (1.28)

16 x 20 (4.9 x 6.1)

16 (4.9)

29 (109.8)

25.0 (1.73)

29 (109.8)

25.0 (1.73)

12 x 12 (3.6 x 3.6)

12 (3.6)

22 (83.3)

14.4 (1.0)

22 (83.3)

14.4 (1.0)

6 to 12 (152 to 305)

14 x 14 (4.3 x 4.3)

14 (4.3)

22 (83.3)

14.4 (1.0)

22 (83.3)

14.4 (1.0)

16 x 16 (4.9 x 4.9)

16 (4.9)

26 (98.4)

20.1 (1.39)

26 (98.4)

20.1 (1.39)

16 x 18 (4.9 x 5.5)

16 (4.9)

31 (117.4)

28.6 (1.97)

31 (117.4)

28.6 (1.97)

Summary of Contents for F1 Res 30 LL

Page 1: ...L Recessed Pendent FP F1Res49LL 58LLRecessed Pendent F1 F1 Res 30 LL Recessed Pendent F2 F1 Res 44 LL 58 LL Recessed HSW F2 F1 Res 30 LL 49 LL 58 LL CCP Pendent F1 Res 44 LL SWC Product Description Model F1 Res LL Pendent sprinklers Figs 1 2 3 4 are fast response sprinklers combining excellent durability high sensitivity glass bulb and low profile decorative design The F1 Res LL Horizontal Sidewal...

Page 2: ...el F1 Res LL sprinklers Use of any other recessed escutcheon will void all approvals and warranties For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin kler Wrench for installing Models F1 Res LL Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench Use o...

Page 3: ... 79 100 150 38 66 4 9 70 6 2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 13 49 7 0 0 48 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or ...

Page 4: ...2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 61 7 6 0 53 16 61 7 6 0 53 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3...

Page 5: ... Ft m Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 Smooth Ceilings 1 2 to 1 13mm to 25mm using CCP or FP escutcheon Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3 14 4 3 13 49 7 0 0 48 16 x 16 4 9 x 4 9 16 4 9 14 53 8 2 0 56 18 x 18 5 5 x 5 5 18 5 5 18 68 1 13 5 0 93 20 x 20 6 1 x 6 1 20 6 1 20 75 7 16 7 1 14 Note Sprinklers shown in Fig 3 and Fig 4 are n...

Page 6: ...nch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 12 45 4 7 5 0 52 12 45 4 7 5 0 52 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 14 53 0 10 2 0 71 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 16 4 9 16 60 6 13 3 0 92 16 60 6 13 3 0 92 16 x 18 4 9 x 5 5 16 4 9 18 68 1 16 8 0 53 18 68 1 16 8 0 53 18 x 18 5 5 x 5 5 18 5 5 19 72 0 18 7 1 29...

Page 7: ...Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 60 6 7 6 0 53 16 60 6 7 6 0 53 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 18 68 2 9 7 0 69 18 68 2 9 7 0 69 16 x 16 4 9 x 4 9 16 4 9 21 79 5 13 2 0 91 21 79 5 13 2 0 91 16 x 18 4 9 x 5 5...

Page 8: ...del F1 Res 30 LL 49 LL 58 LL Recessed Pendent FP Specifications Sprinklers shall be cULus Listed WaterMark Certified WMCS low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0 05 gpm ft2 over the listed coverage area Listed flows as specified by the manufacturer s technical data sheets are to be used Residential sprinklers shall be installed in con fo...

Page 9: ...ld head cup with 3 mm glass bulb containing no plas tic parts and having a temperature rating of 155 F 68 C 175 F 79 C Sprinklers shall have a nominal K factor of 4 4 62 8 Standard finish Bronze Chrome plated White Polyester Special finish specify Residential hori zontal sidewall sprinklers shall be Reliable Model F1 Res 44 LL SIN RA3331 Bulletin 033 Model F1 Res 44 LL Recessed Horizontal Sidewall...