Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 033 Februar

y 2019

Bulletin 033 February 2019

Model F1 RES LL
Residential Sprinklers 

Types:

1.  F1 Res 30 LL Pendent
2.  F1 Res 30 LL Recessed Pendent/F2
3.  F1 Res 30 LL Recessed Pendent/FP
4.  F1 Res 49 LL Pendent
5.  F1 Res 49 LL Recessed Pendent/F1
6.  F1 Res 49 LL Recessed Pendent/FP
7.  F1 Res 58 LL Pendent
8.  F1 Res 58 LL Recessed Pendent/F1
9.  F1 Res 58 LL Recessed Pendent/FP
10.  F1 Res 30 LL CCP Pendent
11.  F1 Res 49 LL CCP Pendent
12.  F1 Res 58 LL CCP Pendent
13.  F1 Res 44 LL HSW
14.  F1 Res 44 LL Recessed HSW/F2
15.  F1 Res 58 LL HSW
16.  F1 Res 58 LL HSW Recessed HSW/F2
17.  F1 Res 44 LL SWC

Listings & Approvals 

1.  Listed by Underwriters Laboratories Inc. and

UL Certified for Canada  (cULus) for Safety to ANSI/
UL1626.

2.  Certified by Underwriters Laboratories, Inc. and Under-

writers Laboratories of Canada for Health Effects to NSF/
ANSI Standard 61 Annex G (Less than 0.25% Lead Con-
tent.)

3.  WaterMark certified. WaterMark Certificate Number 

23347

Additional Bulletins applicable to all
F1RES LL Sprinklers

•  Wall Wetting - Bulletin 007
•  Design and Installation - Bulletin 140

UL Listing Category

Residential Automatic Sprinkler

UL Guide Number

VKKW

Patents

US Patent No. 6,516,893 applies to the 
Model F1 Res 49 LL & 58 LL Pendent Sprinklers
Other patents pending.

F1 Res 30 LL, 49 LL, & 58 

LL Recessed Pendent/FP

F1 Res 49 LL & 58 LL Recessed 

Pendent / F1, F1 Res 30 LL

Recessed Pendent/F2

F1 Res 44 LL & 58 LL 

Recessed HSW/F2

 F1 Res 30 LL, 49 LL & 58 LL

CCP Pendent

F1 Res 44 LL

SWC

Product Description

Model F1 Res LL Pendent sprinklers (Figs. 1, 2, 3, & 4) are 

fast response sprinklers combining excellent durability, high 
sensitivity glass-bulb and low profile decorative  design.  The 
F1 Res LL Horizontal Sidewall sprinklers (Figs. 5, & 6) are 
equally attractive when above ceiling piping cannot be used.  

The 3mm glass-bulb pendent sprinklers permit the efficient 

use of residential water supplies for sprinkler coverage in resi-
dential fire protection design.

The low flow F1 Res LL sprinklers are specially engineered 

for fast thermal response to meet the sensitive fire protection 
application needs of the latest residential market standards 
(UL 1626 Standard).  Upon fire conditions, rising heat causes 
a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the 
waterway for water flow onto the deflector, evenly distributing 
the discharged water to control a fire.

Technical Data:

•  Thermal Sensor:  Nominal 3mm glass-bulb 
•  Sprinkler Frame :  Brass
•  Sprinklers’ Pressure Rating :  175 psi

Factory Hydrostatically Tested to 500 psi 

•  Thread Size:  ½” NPT (R½)
•  K-Factor:  3.0  (Actual)  -  F1  Res  30  LL  Pendent  Sprinkler                            

4.9 (Actual) - F1 Res 49 LL Pendent Sprinkler 
5.8  (Actual) - F1 Res 58 LL Pendent & HSW Sprinkler
4.4 (Actual) - F1 Res 44 LL HSW Sprinkler

Specifically Listed for use in Multipurpose Systems that serve both 
domestic water and fire protection.

F1 Res 30 LL, 49 LL & 58 LL

Pendent

F1 Res 44 LL & 58 LL

HSW

Summary of Contents for F1 Res 30 LL

Page 1: ...L Recessed Pendent FP F1Res49LL 58LLRecessed Pendent F1 F1 Res 30 LL Recessed Pendent F2 F1 Res 44 LL 58 LL Recessed HSW F2 F1 Res 30 LL 49 LL 58 LL CCP Pendent F1 Res 44 LL SWC Product Description Model F1 Res LL Pendent sprinklers Figs 1 2 3 4 are fast response sprinklers combining excellent durability high sensitivity glass bulb and low profile decorative design The F1 Res LL Horizontal Sidewal...

Page 2: ...el F1 Res LL sprinklers Use of any other recessed escutcheon will void all approvals and warranties For installing Model F1 Res LL Pendent sprinklers use only the Model W2 sprin kler Wrench for installing Models F1 Res LL Recessed Pendent CCP SWC sprinklers use only the Model GFR2 sprinkler wrench for installing Model F1 LL Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench Use o...

Page 3: ... 79 100 150 38 66 4 9 70 6 2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 13 49 7 0 0 48 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or ...

Page 4: ...2 25 57 Max Coverage area Ft x Ft m x m Max Spacing Ft m Ordinary Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 61 7 6 0 53 16 61 7 6 0 53 Smooth Ceilings 1 to 4 25mm to 100mm Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3...

Page 5: ... Ft m Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 13 49 7 0 0 48 Smooth Ceilings 1 2 to 1 13mm to 25mm using CCP or FP escutcheon Beamed Ceilings per NFPA 13 13D or 13R 8 2 4 14 x 14 4 3 x 4 3 14 4 3 13 49 7 0 0 48 16 x 16 4 9 x 4 9 16 4 9 14 53 8 2 0 56 18 x 18 5 5 x 5 5 18 5 5 18 68 1 13 5 0 93 20 x 20 6 1 x 6 1 20 6 1 20 75 7 16 7 1 14 Note Sprinklers shown in Fig 3 and Fig 4 are n...

Page 6: ...nch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 12 45 4 7 5 0 52 12 45 4 7 5 0 52 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 14 53 0 10 2 0 71 14 53 0 10 2 0 71 16 x 16 4 9 x 4 9 16 4 9 16 60 6 13 3 0 92 16 60 6 13 3 0 92 16 x 18 4 9 x 5 5 16 4 9 18 68 1 16 8 0 53 18 68 1 16 8 0 53 18 x 18 5 5 x 5 5 18 5 5 19 72 0 18 7 1 29...

Page 7: ...Temp Rating 155 F 68 C Intermediate Temp Rating 175 F 79 C Top of Deflector to Ceiling Inch mm Minimum Spacing Ft m Flow GPM L min Pressure PSI bar Flow GPM L min Pressure PSI bar 12 x 12 3 6 x 3 6 12 3 6 16 60 6 7 6 0 53 16 60 6 7 6 0 53 4 to 6 100 to 152 8 2 4 14 x 14 4 3 x 4 3 14 4 3 18 68 2 9 7 0 69 18 68 2 9 7 0 69 16 x 16 4 9 x 4 9 16 4 9 21 79 5 13 2 0 91 21 79 5 13 2 0 91 16 x 18 4 9 x 5 5...

Page 8: ...del F1 Res 30 LL 49 LL 58 LL Recessed Pendent FP Specifications Sprinklers shall be cULus Listed WaterMark Certified WMCS low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0 05 gpm ft2 over the listed coverage area Listed flows as specified by the manufacturer s technical data sheets are to be used Residential sprinklers shall be installed in con fo...

Page 9: ...ld head cup with 3 mm glass bulb containing no plas tic parts and having a temperature rating of 155 F 68 C 175 F 79 C Sprinklers shall have a nominal K factor of 4 4 62 8 Standard finish Bronze Chrome plated White Polyester Special finish specify Residential hori zontal sidewall sprinklers shall be Reliable Model F1 Res 44 LL SIN RA3331 Bulletin 033 Model F1 Res 44 LL Recessed Horizontal Sidewall...