background image

8.

11.  Upon seeing this solid flow of water coming out of the 

Model LP Dry Valve Actuator, open valves M (Rapid-Air 
Fill Shutoff Valve) and K (Regulated Air Shutoff Valve), 
thereby rapidly applying compressed air or nitrogen 
into the Model LP Dry Valve Actuator (and the sprinkler 
system) until the pressure conforms to Table A levels, as 
indicated by the system air pressure gauge.  The Model 
LP Dry Valve Actuator will eventually close during this 
pressurizing process and the water will stop flowing into 
the drip cup. At this point, the pressure gauge which 
indicates push-rod chamber pressure will equalize to 
the available water supply pressure.  Once the actuator 
is setup correctly, close the Rapid-Air Fill Shutoff Valve, 
valve M.  Keep the Regulated Air Shutoff Valve, valve 
K open.  

Note:

  If 1) the optional air compressor is in-

stalled and 2) the dryness of the supervisory air is criti-
cal (i.e. freezer applications), valve G should be closed 
during this step as to not let any moist air into the sprin-
kler system.  Valve G may be re-opened once the Model 
LP Dry Valve Actuator has been successfully set up with 
a dry air supply (i.e., nitrogen) in order to provide any 
make up air that, if not supplied, could cause a potential 
low-air alarm condition.

12.  Open valve N.
13.  If the Model B1 Accelerator Kit is installed, open valve 

P.  Prior to opening valve P, be sure that the Model B1 
Accelerator has been successfully reset per Reliable 
Technical Bulletin 323.  

Note:

 The B1 Accelerator re-

quires a minimum of 15 psi (1.0 bar) of supervisory gas 
pressure for proper operation. 

14.  Close the manual pull station that is assembled to the 

exterior of the PrePaK’s 24VDC Terminal Box and then 
press the system reset button on the Potter PFC-4410-
RC Panel. 

Note:

 All other detection devices must be 

reset before the releasing/control panel can be reset. 

15.  Slightly open the main valve controlling water supply to 

the Model DDX Deluge Valve.  This will fill the deluge 
valve’s volume beneath its clapper with water.  Slightly 
open the main drain valve, valve B, to vent any trapped 
air. Once any trapped air has been vented, close valve 
B.  Making sure that valve N is open, observe if water 
leaks through the ball drip valve, valve F, into the drip 
cup (Or into the 1” Drain manifold trough the clear tub-
ing for 8” System). If no leakage occurs, the deluge 
valve’s clapper is sealed. Fully open the main valve 
controlling the water supply to the Model DDX Deluge 
Valve.  Visually verify by the position of its indicator flag 
that it is fully-opened. 

16.  Verify that valve A is open. 
17.  Secure the handle of the Model B Manual Emergency 

Station, valve D, in the OFF position with a nylon tie 
(supplied with the assembly). 

18.  Press the system reset button on the Potter PFC-4410-

RC Panel to place the system in the ready condition. 

Note:

 All detection devices must be reset before the 

panel can be reset. 

Inspection And Testing 

Refer to Figs. 10, 11 or 12 (depending on system size)

1. Water 

supply

 — Verify that the valve controlling water 

supply to the deluge valve is opened fully and properly 
monitored.

2. Alarm 

line

 — Verify that valve C is opened and remains 

in this position.

3.  Other trimming valves

 — Verify that valve N is open 

as well as all of the pressure gauge’s ¼” 3-way valves. 
Valves D, E, and H should be closed.

4.  Ball drip valve F

 — Push in on the plunger to be sure 

the ball check is off its seat. If no water appears, the del-
uge valve’s water seat is tight. Inspect the small bleed 
hole located on the underside of the Model DDX Deluge 
Valve’s pushrod chamber for leakage.

5.  System air pressure

 — Verify that system’s air pres-

sure and water supply pressures are in conformance 
with the values posted in Table A.

6. Releasing 

device

 — Check the outlet of the releasing 

device (i.e., solenoid valve, Model LP Dry Valve Actua-
tor or the Model B Manual Emergency Station, valve D) 
for leakage. Also verify that tubing drain lines from re-
leasing devices are not pinched or crushed which could 
prevent proper releasing of the deluge valve.

7. Testing 

alarms

 — Open valve E permitting water from 

the supply to flow to the alarm pressure switch and to 
the mechanical sprinkler alarm (if present).  After test-
ing, close this valve completely. Push in on the plunger 
of ball drip valve F until all of the water has drained from 
the alarm line.

8. Operational 

test

 — Open the Model B Manual Emer-

gency Station, valve D.  

Note:

 An operational test will 

cause the Deluge Valve to open and flow water into the 
sprinkler system.

9. 

Secure the Model B Manual Emergency Station, valve 
D, in the OFF position with a nylon tie (included with the 
assembly) after the deluge valve is reset.

Testing the Model DDX Deluge Valve Without 
Flowing Water 

Refer to Figs. 10, 11 or 12 (depending on system size) 
1.  Close the valve controlling water supply to deluge valve 

and open the main drain valve B. 

2.  Verify that valve A is open, allowing water to enter the 

push rod chamber. 

3.  Close off the air/nitrogen supply to the sprinkler system. 
4.  Decrease pneumatic pressure in the system by open-

ing the ¼” angle valve, valve H, deluge valve until the 
Model LP Dry Valve Actuator operates. This will be in-
dicated by a sudden drop of water pressure on the air 
pressure gauge. This operation of the actuator will vent 
the water pressure from itself back to the solenoid valve 
which is still closed. The push-rod chamber of the del-
uge valve should still be pressurized at this point. 

Summary of Contents for DDX PrePaK

Page 1: ...visory Pressure Double Interlock Electric Pneumatic Release Contents Page General Description 2 Listings and Approvals 2 Technical Data 4 Installation Requirements 5 System Operation 7 System Reset Procedure 7 Inspection Testing and Maintenance 8 Diagrams Assembly Dimensions 3 Potter PFC 4410 RC Releasing Control Panel 10 Terminal Box Wiring 11 Factory Installed Electrical Devices 12 14 Detector C...

Page 2: ...urged of its su pervisory air sufficiently enough for the Model LP Dry Valve Actuator to operate This purging is usually caused by the operation of an automatic sprinkler In the event that the system piping is ruptured or a sprin kler head is accidentally opened the Model LP Dry Valve Actuator will open and a low system air pressure alarm will sound The Model DDX Deluge Valve however will not be r...

Page 3: ...3 Fig 1 ...

Page 4: ...ote controlled Releasing Control Panels used with these units are Listed Approved and programmed to handle the required sequence of operation necessary to operate the automatic sprinkler system Any unauthorized modification or addition made on site to a factory built Listed Approved unit will void the Listing Approval Such modifications or additions may void the unit s warranty as well Consult Re ...

Page 5: ...ditional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period The valve and applicable trim kit have been tested approved and listed under these conditions and as such hydrostatic testing in accordance with NFPA 13 is ac ceptabl...

Page 6: ...y fill the sprinkler system with air the steel enclosure s door should remain open to provide maximum intake air flow to the air compressor The air compressor is connected to a storage tank This tank functions as a reser voir providing make up air to compensate for small inter mittent leaks in the sprinkler system It should be noted that significant leaks may overburden this storage tank thereby c...

Page 7: ...ion Systems provides minimum mainte nance requirements Systems should be tested operated cleaned and inspected at least annually and parts replaced as required Periodically open the air condensate drain valve see Figs 10 11 or 12 depending on system size beneath the air tank to drain any condensate accumulation Reliable Technical Bulletin 751 provide information for maintaining the Model DDX Delug...

Page 8: ...l Emergency Station valve D in the OFF position with a nylon tie supplied with the assembly 18 Press the system reset button on the Potter PFC 4410 RC Panel to place the system in the ready condition Note All detection devices must be reset before the panel can be reset Inspection And Testing Refer to Figs 10 11 or 12 depending on system size 1 Water supply Verify that the valve controlling water ...

Page 9: ...ve B If system contains pressur ized air allow air pressure to come back up to specifica tion Open valve A first and then open the main valve controlling the water supply to the deluge valve 9 SOLENOID VALVE INSPECTIONS TESTS AND MAINTENANCE WARNING THE OWNER IS RESPONSIBLE FOR MAIN TAINING THE FIRE PROTECTION SYSTEM IN PROP ER OPERATING CONDITION ANY SYSTEM MAINTE NANCE OR TESTING THAT INVOLVES P...

Page 10: ...POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1 ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY DISCHARGED FLASHING PRE DISCHARGE RUN PROGRAM SET SELECT FUNCTION SCROLL DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET SCROLL UP BUZZER SILENCE VIEWING ANGLE RED OUTPUT LED STEADY ABORT LAMP TEST 10 ...

Page 11: ...11 Fig 3 ...

Page 12: ...12 Fig 4 ...

Page 13: ...13 Fig 5 ...

Page 14: ...14 Fig 6 ...

Page 15: ...15 Fig 7 ...

Page 16: ...16 Fig 8 ...

Page 17: ...17 Fig 9 ...

Page 18: ...18 Fig 10 ...

Page 19: ...19 ...

Page 20: ...20 Fig 11 ...

Page 21: ...21 ...

Page 22: ...22 Fig 12 ...

Page 23: ...23 ...

Page 24: ...Release 3 Waterflow 4 Low Air Supervisory 1 ALARM X X 2 ALARM X 3 SUPERVISORY X X 4 RELEASE X X INPUTS 1 conventional zone 1 manual release zone 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of either the conventional zone or the manual release will operate the solenoid release cir...

Page 25: ...25 Fig 13 ...

Page 26: ... SUPERVISORY X X 4 RELEASE X X INPUTS 2 conventional zones cross zoned 1 waterflow zone 1 low air zone 1 supervisory zone OUTPUTS 1 general alarm bell 1 waterflow bell 1 supervisory bell 1 solenoid release circuit OPERATION Activation of both conventional zones at the same time will operate the solenoid release circuit and thegeneral alarm bell Activation of either conventional zone will operate t...

Page 27: ...27 Fig 14 ...

Page 28: ...28 Fig 15 ...

Page 29: ...29 Fig 16 ...

Page 30: ...nted in U S A 10 16 P N 9999970383 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association Factory Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable Products manufactured and distributed by Reliable have been...

Reviews: